What does your ActronAir fault code mean?

Pick the code showing on your remote, wall controller or indoor unit and see what it means, what commonly causes it, and what is safe to check yourself. This page covers 207 ActronAir fault codes for units sold in Australia, compiled from official Australian manufacturer and distributor documentation, the same references our own technicians carry.

Heads up: ActronAir uses the same code with different meanings on different product ranges, so check the model range shown next to the code.

Every ActronAir fault code at a glance

Some models show faults as a flashing-light pattern instead of a code; documented lamp patterns are listed alongside their codes.

Code What it means Severity
CP (Aurora (SWB) and Serene (WRC/WRE) wall splits and multi-split indoor units (MRE/BRE) (shown as off by remote switch on multi-splits)) The remote on/off terminal is open, which usually means an external switch or energy management device has turned the unit off. Normal operation
E0 (Aurora (SWB) and Serene (WRC/WRE) wall splits, Cascade (URC/CRE) and UltraSlim (URC/LRE) split ducted and cassette systems and multi-split indoor units (MRE/BRE) (1 lamp flash))
also shown as 1 lamp flash
The indoor unit’s memory chip (EEPROM) has a parameter error. Fault – service needed
E0 (Multi-split outdoor units (MRC)) The outdoor unit’s memory chip (EEPROM) has a parameter error. Fault – service needed
E0 (Systems with the WC-02 wired wall controller (Cascade and UltraSlim ducted and cassette units)) A power phase sequence error or phase failure has been detected (three phase units). Fault – service needed
E01 (Classic 2 (CRA/CCA/EVA/EAA/EFA), Advance (CRV/EVV/EAA/EFV) and Aires (CRS/EVA) ducted systems (NEO, LR7-1 and LC7-2 wall controllers)) The indoor fan is not running at the speed the system asked for (fan RPM feedback error). Fault – service needed
E09 (Classic 2, ESP Platinum (shown as E9), Advance, Aires and QUE ducted systems)
also shown as E9
The low pressure safety switch has tripped, usually because the system is low on refrigerant. Fault – service needed
E1 (Aurora (SWB) and Serene (WRC/WRE) wall splits, Cascade (URC/CRE) and UltraSlim (URC/LRE) split ducted and cassette systems (indoor and outdoor displays, including the UltraSlim R-32 outdoor display), multi-split indoor units (MRE/BRE) (2 lamp flashes) and the WC-02 wired controller)
also shown as 2 lamp flashes
The indoor and outdoor units have lost communication with each other. Fault – service needed
E10 (ESP Platinum, Advance, Aires and QUE ducted systems) The low pressure sensor has failed (open or short circuit). Minor fault
E100 (Advance ducted systems) The drive’s PFC circuit has tripped a hardware overcurrent protection. Fault – service needed
E100 (Aires ducted systems) The compressor drive’s charging circuit has a malfunction. Fault – service needed
E101 (Advance and Aires ducted systems) The drive’s PFC circuit has tripped a software overcurrent protection. Fault – service needed
E102 (Advance and Aires ducted systems) The drive’s PFC circuit has detected excessive voltage. Fault – service needed
E103 (Advance ducted systems with the R-32 (Uno Pro board) outdoor unit and Aires ducted systems)
also shown as E103**
The drive’s power module temperature reading is abnormally low or its sensor is open circuit. Minor fault
E104 (Advance ducted systems with the R-32 (Uno Pro board) outdoor unit and Aires ducted systems)
also shown as E104**
The drive has locked itself out after reaching its fault limit and needs to be reset and checked. Fault – service needed
E11 (Classic 2, ESP Platinum, Advance, Aires and QUE ducted systems) The high pressure safety switch has tripped, usually because the outdoor unit cannot get rid of heat. Fault – service needed
E12 (ESP Platinum, Advance, Aires and QUE ducted systems) The high pressure sensor has failed (open or short circuit). Minor fault
E13 (Advance ducted systems with the R-410A (Uno board) outdoor unit; QUE three phase systems can show the same meaning under E13)
also shown as E13*
The outdoor drive’s HSP connector jumper pin is missing or disconnected. Fault – service needed
E13 (Advance, Aires and QUE three phase ducted systems) The outdoor unit’s compressor drive has reported an internal error. Fault – service needed
E14 (ESP Platinum and QUE single phase ducted systems) The condenser pressure is too low for normal operation. Fault – service needed
E15 (ESP Platinum, Advance, Aires and QUE ducted systems) The outdoor unit has lost communication with its compressor speed drive (VSD). Fault – service needed
E17 (ESP Platinum and QUE single phase ducted systems) A fault has been detected in one of the outdoor unit’s peripheral devices. Fault – service needed
E18 (ESP Platinum, Advance, Aires and QUE ducted systems (E18 open circuit, E19 short circuit on ESP Platinum and QUE single phase))
also shown as E19
The suction temperature sensor has failed or is giving an abnormal reading. Minor fault
E2 (Multi-split outdoor units (MRC)) The indoor and outdoor units have lost communication with each other. Fault – service needed
E2 (Systems with the WC-02 wired wall controller (Cascade and UltraSlim ducted and cassette units)) The room temperature sensor (T1) has failed. Minor fault
E2 (ESP Digital and ESP Plus ducted systems (SRD/SRV) with LM7 or LM24 wall controller) The indoor coil outlet temperature sensor has failed (open or short circuit). Minor fault
E22 (ESP Platinum, Advance, Aires and QUE ducted systems) The outdoor ambient temperature sensor has failed, and the unit may run in a reduced safe mode. Minor fault
E23 (ESP Platinum and QUE single phase ducted systems) The outdoor unit has lost communication with its electronic expansion valve (EEV) board, and the unit runs in safe mode. Fault – service needed
E25 (ESP Platinum and QUE single phase ducted systems) The outdoor temperature reading has not updated, which is a status message rather than a breakdown. Normal operation
E26 (ESP Platinum, Advance, Aires and QUE ducted systems) The compressor drive has detected excessive electrical current and shut down to protect itself. Fault – service needed
E27 (ESP Platinum, Advance, Aires and QUE ducted systems) The compressor drive has detected the incoming voltage is too high. Fault – service needed
E28 (ESP Platinum, Advance, Aires and QUE ducted systems) The compressor drive electronics are running too hot. Fault – service needed
E29 (ESP Platinum, Advance, Aires and QUE ducted systems) The compressor drive has detected the incoming voltage is too low. Fault – service needed
E3 (Aurora (SWB) and Serene (WRC/WRE) wall splits, Cascade (URC/CRE) and UltraSlim (URC/LRE) split ducted and cassette systems and multi-split indoor units (MRE/BRE) (4 lamp flashes))
also shown as 4 lamp flashes
The indoor fan is not running at the correct speed. Fault – service needed
E3 (Multi-split outdoor units (MRC)) The outdoor unit’s inverter (IPM) board has lost communication with the main outdoor control board. Fault – service needed
E3 (Systems with the WC-02 wired wall controller (Cascade and UltraSlim ducted and cassette units)) The indoor coil outlet temperature sensor (T2A) has failed. Minor fault
E3 (Ducted systems on LM7, LM24, LM-ZC, LR7, LC7, NEO and Que controllers (Classic, Classic 2, ESP Digital/Plus, ESP Platinum, Advance, Aires, QUE))
also shown as E03
A room temperature sensor has failed (open or short circuit), so the system cannot read the room temperature properly. Minor fault
E30 (ESP Platinum, Advance, Aires and QUE ducted systems) The compressor drive has locked itself out after repeated faults and needs to be reset and checked. Fault – service needed
E31 (ESP Platinum and QUE single phase ducted systems) The compressor drive has reported an internal error. Fault – service needed
E32 (ESP Platinum and QUE single phase ducted systems)
also shown as E33
The system tripped on high or low refrigerant pressure measured by the drive’s pressure sensors (envelope protection). Fault – service needed
E34 (ESP Platinum and QUE single phase ducted systems) The unit has reduced its output because the compressor drive is running hot (derating). Minor fault
E35 (ESP Platinum and QUE single phase ducted systems) The unit has reduced its output because the suction pressure is low (derating). Minor fault
E36 (ESP Platinum and QUE single phase ducted systems) The unit has reduced its output because the condenser pressure is low (derating). Minor fault
E37 (ESP Platinum and QUE single phase ducted systems) The unit has reduced its output because the condenser pressure is high (derating). Minor fault
E38 (ESP Platinum and QUE single phase ducted systems) The unit has reduced its output to stay within its power limit (derating). Normal operation
E39 (ESP Platinum and QUE single phase ducted systems) A defrost cycle took too long to complete and timed out. Minor fault
E4 (Aurora (SWB) and Serene (WRC/WRE) wall splits, Cascade (URC/CRE) and UltraSlim (URC/LRE) split ducted and cassette systems and multi-split indoor units (MRE/BRE) (5 lamp flashes))
also shown as 5 lamp flashes
The indoor room temperature sensor (T1) has failed (open or short circuit). Minor fault
E4 (Multi-split outdoor units (MRC)) An outdoor temperature sensor (coil T3, ambient T4, discharge T5 or indoor coil outlet pipe T2B) has failed. Minor fault
E4 (Systems with the WC-02 wired wall controller (Cascade and UltraSlim ducted and cassette units)) The indoor coil outlet pipe temperature sensor (T2B) has failed. Minor fault
E4 (Ducted systems on LM7, LM24, LR7, LC7, NEO and Que controllers (Classic, Classic 2, ESP Digital/Plus, ESP Platinum, Advance, Aires, QUE; the QUE three phase table reads it as the indoor coil out sensor))
also shown as E04
The indoor coil temperature sensor has failed (open or short circuit). Minor fault
E40 (ESP Platinum and QUE single phase ducted systems) The compressor drive is restarting too frequently, which points to an underlying problem. Fault – service needed
E41 (ESP Platinum, Advance, Aires and QUE ducted systems) The compressor drive’s internal DC voltage is too low. Fault – service needed
E42 (Advance, Aires and QUE three phase ducted systems) The system shut down to protect the compressor because the evaporating pressure fell extremely low (envelope protection). Fault – service needed
E43 (Advance, Aires and QUE three phase ducted systems) The system shut down to protect the compressor because the compression ratio was too high (envelope protection). Fault – service needed
E44 (Advance, Aires and QUE three phase ducted systems) The system shut down because the condensing pressure was too high (envelope protection). Fault – service needed
E45 (Advance, Aires and QUE three phase ducted systems) The system shut down because the compression ratio was too low (envelope protection). Fault – service needed
E47 (Advance, Aires and QUE three phase ducted systems) The compressor hit its torque limit and the system shut down to protect it. Fault – service needed
E5 (Aurora (SWB) and Serene (WRC/WRE) wall splits, Cascade (URC/CRE) and UltraSlim (URC/LRE) split ducted and cassette systems and multi-split indoor units (MRE/BRE) (6 lamp flashes))
also shown as 6 lamp flashes
The indoor coil temperature sensor (T2) has failed (open or short circuit). Minor fault
E5 (Multi-split outdoor units (MRC)) The supply voltage to the outdoor unit is too high or too low. Fault – service needed
E5 (Systems with the WC-02 wired wall controller (Cascade and UltraSlim ducted and cassette units)) An outdoor temperature sensor (T3 coil or TP discharge) has failed. Minor fault
E5 (Classic (SRA/SRE/SRG), ESP Digital/Plus (SRD/SRV) and ESP Platinum ducted systems; QUE single phase shows E05 on the outdoor display)
also shown as E05
The indoor and outdoor units have lost communication with each other. Fault – service needed
E50 (Advance, Aires and QUE three phase ducted systems) The outdoor control board is not configured correctly for the unit. Fault – service needed
E51 (Classic 2, Advance, Aires and QUE ducted systems (NEO, LR7-1, LC7-2 or Que controllers)) The indoor and outdoor units have lost communication with each other. Fault – service needed
E52 (Classic 2, Advance, Aires and QUE ducted systems (NEO, LR7-1, LC7-2 or Que controllers)) The indoor unit has lost communication with the wall controller. Fault – service needed
E53 (QUE ducted systems with Que zoning (single and three phase)) The indoor unit has lost communication with the zone (VAV) module. Fault – service needed
E55 (Classic 2, Advance and Aires ducted systems (NEO, LR7-1 or LC7-2 wall controller)) The outdoor unit has lost communication with the building management system (BMS) interface. Minor fault
E56 (Classic 2, Advance and Aires ducted systems (NEO, LR7-1 or LC7-2 wall controller)) The system cannot find a master wall controller. Fault – service needed
E6 (Multi-split outdoor units (MRC)) The power factor correction (PFC) module in the outdoor unit has tripped a protection. Fault – service needed
E6 (Systems with the WC-02 wired wall controller (Cascade and UltraSlim ducted and cassette units)) The indoor circuit board’s zero crossing check has failed (a power signal fault on the board). Fault – service needed
E6 (Most ActronAir ducted systems (Classic, ESP Digital/Plus, ESP Platinum, Advance, Aires, QUE; LM7, LM24, LR7, NEO and Que controllers))
also shown as E06
The compressor discharge temperature is too high, which often means the system is low on refrigerant. Fault – service needed
E60 (Advance, Aires and QUE three phase ducted systems) The compressor drive has detected excessive current in a compressor phase and shut down. Urgent – turn it off
E61 (Advance and Aires ducted systems) The compressor drive has lost one of the compressor’s output phases. Fault – service needed
E62 (Advance, Aires and QUE three phase ducted systems) The compressor drive’s internal DC bus voltage is too high. Fault – service needed
E63 (Advance, Aires and QUE three phase ducted systems) The compressor drive’s internal DC bus voltage is too low. Fault – service needed
E64 (Advance ducted systems) The compressor drive has lost track of the compressor rotor and stopped it. Fault – service needed
E65 (Advance ducted systems) The current sensor for the compressor’s U phase has failed. Fault – service needed
E65 (Aires ducted systems) The compressor drive has detected a compressor phase loss fault. Fault – service needed
E66 (Advance ducted systems with the R-410A (Uno board) outdoor unit and QUE three phase systems)
also shown as E66*
The incoming AC supply voltage is imbalanced between phases or an input phase has been lost. Fault – service needed
E67 (Advance ducted systems with the R-410A (Uno board) outdoor unit and QUE three phase systems)
also shown as E67*
The compressor drive’s inverter has tripped a de-saturation (hardware overcurrent) protection. Fault – service needed
E68 (Advance ducted systems) The current sensor for the compressor’s V phase has failed. Fault – service needed
E69 (Advance, Aires and QUE three phase ducted systems) The drive’s power factor correction (PFC-IGBT) module is running too hot. Fault – service needed
E7 (Serene (WRC/WRE) wall splits and multi-split indoor units (MRE/BRE)) The indoor unit’s display board has lost communication with the main indoor circuit board. Minor fault
E7 (Systems with the WC-02 wired wall controller (Cascade and UltraSlim ducted and cassette units)) The indoor unit’s memory chip (EEPROM) has a fault. Fault – service needed
E7 (Most ActronAir ducted systems (Classic, Classic 2, ESP Digital/Plus, ESP Platinum, Advance, Aires, QUE; LM7, LM24, LR7, NEO and Que controllers))
also shown as E07
The outdoor coil temperature sensor has failed (open or short circuit). Minor fault
E70 (Advance, Aires and QUE three phase ducted systems) The compressor drive has lost the compressor rotor position and stopped it. Fault – service needed
E71 (Advance, Aires and QUE three phase ducted systems) The compressor motor temperature sensor (thermistor) has failed. Minor fault
E72 (Advance, Aires and QUE three phase ducted systems) The drive’s precharge relay is stuck open, so the drive cannot power up properly. Fault – service needed
E73 (Advance and Aires ducted systems) The current sensor for the compressor’s W phase has failed. Fault – service needed
E74 (Advance and Aires ducted systems) The drive has tripped on IGBT overcurrent, which can point to a choke wiring problem or failure. Urgent – turn it off
E74 (QUE three phase ducted systems) The compressor drive has detected excessive current in a compressor phase and shut down. Urgent – turn it off
E75 (Advance, Aires and QUE three phase ducted systems) The drive kept reducing compressor speed because of high phase current until it timed out (foldback timeout). Fault – service needed
E76 (Advance, Aires and QUE three phase ducted systems) The drive kept reducing output because its power module was too hot until it timed out (foldback timeout). Fault – service needed
E77 (Advance, Aires and QUE three phase ducted systems) The drive kept reducing output because of high AC input current until it timed out (foldback timeout). Fault – service needed
E78 (Advance and Aires ducted systems) The drive’s power factor correction (PFC-IGBT) module temperature is abnormally low. Minor fault
E78 (QUE three phase ducted systems) The drive’s automatic configuration communication has timed out. Fault – service needed
E79 (Advance and Aires ducted systems) The drive has tripped a hardware overcurrent (IPM) protection on the compressor. Urgent – turn it off
E8 (Cascade (URC/CRE) and UltraSlim (URC/LRE) twin systems (indoor display, 9 lamp flashes))
also shown as 9 lamp flashes
The master and slave indoor units of a twin system have lost communication with each other. Fault – service needed
E8 (Multi-split outdoor units (MRC)) The outdoor fan is not running at the correct speed. Fault – service needed
E8 (Systems with the WC-02 wired wall controller (Cascade and UltraSlim ducted and cassette units)) The indoor fan controller is out of control (the fan is not responding correctly). Fault – service needed
E8 (ESP Digital/Plus, ESP Platinum, Advance, Aires and QUE ducted systems (not the original Classic series))
also shown as E08
The outdoor discharge temperature sensor has failed (open or short circuit). Minor fault
E80 (Advance, Aires and QUE three phase ducted systems) The compressor motor temperature is too high. Fault – service needed
E81 (Advance, Aires and QUE three phase ducted systems) The compressor drive’s control board temperature is too high. Fault – service needed
E82 (Advance, Aires and QUE three phase ducted systems) The compressor drive’s power module temperature is too high. Fault – service needed
E83 (Advance, Aires and QUE three phase ducted systems) The drive’s power factor correction (PFC-IGBT) module temperature is too high. Fault – service needed
E84 (Advance, Aires and QUE three phase ducted systems) Communication has been lost between two processors (DSP and PFC) inside the compressor drive. Fault – service needed
E85 (Advance, Aires and QUE three phase ducted systems) Communication has been lost between the drive’s communications processor and its DSP. Fault – service needed
E86 (Advance and QUE three phase ducted systems) The current drawn by the compressor phases is imbalanced. Fault – service needed
E87 (Advance and QUE three phase ducted systems) The current in the drive’s three phase PFC circuit is imbalanced. Fault – service needed
E88 (Advance ducted systems with the R-32 (Uno Pro board) outdoor unit, Aires and QUE three phase systems)
also shown as E88**
The compressor drive has a microelectronics or memory (EEPROM) fault. Fault – service needed
E89 (Advance and QUE three phase ducted systems) The compressor motor ran over its speed limit and the drive shut it down. Fault – service needed
E9 (Cascade (URC/CRE) and UltraSlim (URC/LRE) twin systems (indoor display, 10 lamp flashes))
also shown as 10 lamp flashes
Another indoor unit in the twin system has a fault. Fault – service needed
E9 (Systems with the WC-02 wired wall controller (Cascade and UltraSlim ducted and cassette units)) The main indoor circuit board has lost communication with the display board. Minor fault
E9 (Classic (SRA/SRE/SRG) and ESP Digital/Plus (SRD/SRV) ducted systems with LM7 or LM24 wall controller) A refrigerant pressure switch has tripped on high or low pressure, or a power phase problem has been detected (phase faults on three phase units). Fault – service needed
E90 (Advance, Aires and QUE three phase ducted systems) The drive is configured for the wrong compressor model. Fault – service needed
E91 (Advance, Aires and QUE three phase ducted systems) The temperatures measured inside the inverter are imbalanced. Fault – service needed
E92 (Advance, Aires and QUE three phase ducted systems) The temperatures measured in the drive’s PFC circuit are imbalanced. Fault – service needed
E93 (Advance and Aires ducted systems) The compressor motor temperature reading is abnormally low. Minor fault
E94 (Advance and Aires ducted systems) The compressor drive’s board temperature reading is abnormally low. Minor fault
E95 (Advance and Aires ducted systems) The drive’s power module temperature reading is abnormally low or its sensor has failed (open or short circuit). Minor fault
E96 (Advance ducted systems) The drive’s power factor correction (PFC-IGBT) module temperature is abnormally low. Minor fault
E96 (Aires ducted systems) The temperature sensing circuit for the drive’s PFC module has a malfunction. Minor fault
E97 (Advance ducted systems) The drive’s communications analog to digital converter (ADC) has failed. Fault – service needed
E97 (Aires ducted systems) A processor chip (IC) inside the compressor drive has reset unexpectedly. Fault – service needed
E98 (Advance and Aires ducted systems) A current sensor or current sensing circuit in the compressor drive has failed. Fault – service needed
E99 (Advance ducted systems) The compressor drive has tripped on compressor overload. Fault – service needed
E99 (Aires ducted systems) The compressor drive has reported a malfunction outside the standard list. Fault – service needed
E99 (QUE single phase ducted systems) The system shut down on compressor envelope protection. Fault – service needed
EA (Systems with the WC-02 wired wall controller (Cascade and UltraSlim ducted and cassette units)) The compressor has tripped its overload protection (recorded after 4 trips). Fault – service needed
EB (Systems with the WC-02 wired wall controller (Cascade and UltraSlim ducted and cassette units)) The inverter power module (IPM) has a malfunction. Fault – service needed
EC (Aurora (SWB) and Serene (WRC/WRE) wall splits and Cascade (URC/CRE) and UltraSlim (URC/LRE) split ducted and cassette systems (7 lamp flashes))
also shown as 7 lamp flashes
The system has detected a possible refrigerant leak. Urgent – turn it off
EC (Systems with the WC-02 wired wall controller (Cascade and UltraSlim ducted and cassette units)) The air clean function has a malfunction. Minor fault
EC07 (Cascade R-32 (URC/CRC) and UltraSlim R-32 (URC/LRE/LRC) systems; Serene Series 2 R-32 wall splits show the same codes)
also shown as 12 lamp flashes
The outdoor fan is running outside its normal speed range (some models). Fault – service needed
EC0D (Cascade R-32 (URC/CRC) and UltraSlim R-32 (URC/LRE/LRC) systems; Serene Series 2 R-32 wall splits show the same codes)
also shown as 14 lamp flashes
The outdoor unit has reported a malfunction; the outdoor display carries the detailed code. Fault – service needed
EC51 (Cascade R-32 (URC/CRC) and UltraSlim R-32 (URC/LRE/LRC) systems; Serene Series 2 R-32 wall splits show the same codes)
also shown as 5 lamp flashes
The outdoor unit’s memory chip (EEPROM) has a parameter error. Fault – service needed
EC52 (Cascade R-32 (URC/CRC) and UltraSlim R-32 (URC/LRE/LRC) systems; Serene Series 2 R-32 wall splits show the same codes)
also shown as 5 lamp flashes
The outdoor coil temperature sensor (T3) has failed (open or short circuit). Minor fault
EC53 (Cascade R-32 (URC/CRC) and UltraSlim R-32 (URC/LRE/LRC) systems; Serene Series 2 R-32 wall splits show the same codes)
also shown as 5 lamp flashes
The outdoor air temperature sensor (T4) has failed (open or short circuit). Minor fault
EC54 (Cascade R-32 (URC/CRC) and UltraSlim R-32 (URC/LRE/LRC) systems; Serene Series 2 R-32 wall splits show the same codes)
also shown as 5 lamp flashes
The compressor discharge temperature sensor (TP) has failed (open or short circuit). Minor fault
EC56 (Cascade R-32 (URC/CRC) and UltraSlim R-32 (URC/LRE/LRC) systems; Serene Series 2 R-32 wall splits show the same codes (free-match indoor units))
also shown as 5 lamp flashes
The evaporator coil outlet temperature sensor (T2B) has failed (open or short circuit). Minor fault
ED (Systems with the WC-02 wired wall controller (Cascade and UltraSlim ducted and cassette units)) The outdoor unit has a protection fault; the outdoor display carries the detailed code. Fault – service needed
EE (Cascade (URC/CRE) and UltraSlim (URC/LRE) split ducted and cassette systems and multi-split indoor units (MRE/BRE) (cassette and ducted units, 8 lamp flashes); shown as EE full water alarm on the WC-02 wired controller)
also shown as 8 lamp flashes
The condensate water level alarm has activated, meaning the drain system cannot get rid of water. Fault – service needed
EF (Systems with the WC-02 wired wall controller (Cascade and UltraSlim ducted and cassette units)) A fault outside the standard list has been detected (other fault). Minor fault
EH00 (Cascade R-32 (URC/CRC) and UltraSlim R-32 (URC/LRE/LRC) systems; Serene Series 2 R-32 wall splits show the same codes)
also shown as EH0A, 1 lamp flash
The indoor unit’s memory chip (EEPROM) has a parameter error. Fault – service needed
EH03 (Cascade R-32 (URC/CRC) and UltraSlim R-32 (URC/LRE/LRC) systems; Serene Series 2 R-32 wall splits show the same codes)
also shown as 4 lamp flashes
The indoor fan is running outside its normal speed range (some models). Fault – service needed
EH0E (Cascade R-32 (URC/CRC) and UltraSlim R-32 (URC/LRE/LRC) systems; Serene Series 2 R-32 wall splits show the same codes (cassette and ducted units))
also shown as 13 lamp flashes
The condensate water level alarm has activated, meaning the drain system cannot get rid of water. Fault – service needed
EH0b (Cascade R-32 (URC/CRC) and UltraSlim R-32 (URC/LRE/LRC) systems; Serene Series 2 R-32 wall splits show the same codes)
also shown as 9 lamp flashes
The two processor chips on the indoor unit have lost communication with each other. Minor fault
EH3A (Cascade R-32 (URC/CRC) and UltraSlim R-32 (URC/LRE/LRC) systems; Serene Series 2 R-32 wall splits show the same codes (units with an external fan module))
also shown as 4 lamp flashes
The external fan module’s DC bus voltage is too low. Fault – service needed
EH3b (Cascade R-32 (URC/CRC) and UltraSlim R-32 (URC/LRE/LRC) systems; Serene Series 2 R-32 wall splits show the same codes (units with an external fan module))
also shown as 4 lamp flashes
The external fan module’s DC bus voltage is too high. Fault – service needed
EH60 (Cascade R-32 (URC/CRC) and UltraSlim R-32 (URC/LRE/LRC) systems; Serene Series 2 R-32 wall splits show the same codes)
also shown as 6 lamp flashes
The indoor room temperature sensor (T1) has failed (open or short circuit). Minor fault
EH61 (Cascade R-32 (URC/CRC) and UltraSlim R-32 (URC/LRE/LRC) systems; Serene Series 2 R-32 wall splits show the same codes)
also shown as 6 lamp flashes
The indoor coil temperature sensor (T2) has failed (open or short circuit). Minor fault
EHbA (Cascade R-32 (URC/CRC) and UltraSlim R-32 (URC/LRE/LRC) systems; Serene Series 2 R-32 wall splits show the same codes (units with an external fan module)) The external fan module has lost communication with the indoor unit. Minor fault
EL01 (Cascade R-32 (URC/CRC) and UltraSlim R-32 (URC/LRE/LRC) systems; Serene Series 2 R-32 wall splits show the same codes)
also shown as 2 lamp flashes
The indoor and outdoor units have lost communication with each other. Fault – service needed
EL0C (Cascade R-32 (URC/CRC) and UltraSlim R-32 (URC/LRE/LRC) systems; Serene Series 2 R-32 wall splits show the same codes)
also shown as 8 lamp flashes
The system has detected a possible refrigerant leak (some models). Urgent – turn it off
F0 (Serene (WRC/WRE) wall splits and Cascade (URC/CRE) and UltraSlim (URC/LRE) split ducted and cassette systems (some units, 1 lamp flash); also the outdoor display on Cascade, UltraSlim and UltraSlim R-32 systems)
also shown as 1 lamp flash
Overcurrent or overload protection has tripped. Urgent – turn it off
F0 (Systems with the WC-02 wired wall controller (Cascade and UltraSlim ducted and cassette units)) The wired wall controller has lost communication with the indoor unit. Fault – service needed
F1 (Aurora (SWB) and Serene (WRC/WRE) wall splits, Cascade (URC/CRE) and UltraSlim (URC/LRE) split ducted and cassette systems (indoor and outdoor displays, including the UltraSlim R-32 outdoor display) and multi-split indoor units (MRE/BRE) (2 lamp flashes))
also shown as 2 lamp flashes
The outdoor air temperature sensor (T4) has failed (open or short circuit). Minor fault
F1 (Multi-split outdoor units (MRC)) The coil outlet temperature sensor for indoor unit A has failed. Minor fault
F1 (Systems with the WC-02 wired wall controller (Cascade and UltraSlim ducted and cassette units)) The elevating fascia panel has not closed properly. Minor fault
F2 (Aurora (SWB) and Serene (WRC/WRE) wall splits, Cascade (URC/CRE) and UltraSlim (URC/LRE) split ducted and cassette systems (indoor and outdoor displays, including the UltraSlim R-32 outdoor display) and multi-split indoor units (MRE/BRE) (3 lamp flashes))
also shown as 3 lamp flashes
The outdoor coil temperature sensor (T3) has failed (open or short circuit). Minor fault
F2 (Multi-split outdoor units (MRC)) The coil outlet temperature sensor for indoor unit B has failed. Minor fault
F3 (Aurora (SWB) and Serene (WRC/WRE) wall splits, Cascade (URC/CRE) and UltraSlim (URC/LRE) split ducted and cassette systems (indoor and outdoor displays, including the UltraSlim R-32 outdoor display) and multi-split indoor units (MRE/BRE) (4 lamp flashes))
also shown as 4 lamp flashes
The compressor discharge temperature sensor (T5) has failed (open or short circuit). Minor fault
F3 (Multi-split outdoor units (MRC)) The coil outlet temperature sensor for indoor unit C has failed. Minor fault
F4 (Aurora (SWB) and Serene (WRC/WRE) wall splits, Cascade (URC/CRE) and UltraSlim (URC/LRE) split ducted and cassette systems (indoor and outdoor displays, including the UltraSlim R-32 outdoor display) and multi-split indoor units (MRE/BRE) (5 lamp flashes))
also shown as 5 lamp flashes
The outdoor unit’s memory chip (EEPROM) has a parameter error. Fault – service needed
F4 (Multi-split outdoor units (MRC)) The coil outlet temperature sensor for indoor unit D has failed. Minor fault
F5 (Aurora (SWB) and Serene (WRC/WRE) wall splits, Cascade (URC/CRE) and UltraSlim (URC/LRE) split ducted and cassette systems (indoor and outdoor displays, including the UltraSlim R-32 outdoor display) and multi-split indoor units (MRE/BRE) (6 lamp flashes))
also shown as 6 lamp flashes
The outdoor fan is not running at the correct speed. Fault – service needed
F5 (Multi-split outdoor units (MRC)) The coil outlet temperature sensor for indoor unit E has failed. Minor fault
F6 (Cascade and UltraSlim free-match indoor units and multi-split indoor units (MRE/BRE) (7 lamp flashes))
also shown as 7 lamp flashes
The indoor coil outlet pipe temperature sensor (T2B) has failed (open or short circuit). Minor fault
F7 (Cascade slim cassettes with an auto-lifting panel (8 lamp flashes))
also shown as 8 lamp flashes
The auto-lifting panel has lost communication with the slim cassette unit. Minor fault
F8 (Cascade slim cassettes with an auto-lifting panel (9 lamp flashes))
also shown as 9 lamp flashes
The auto-lifting panel mechanism is faulty. Minor fault
F9 (Cascade slim cassettes with an auto-lifting panel (10 lamp flashes))
also shown as 10 lamp flashes
The auto-lifting panel has not closed properly. Minor fault
J0 (Cascade (URC/CRE), UltraSlim (URC/LRE) and UltraSlim R-32 (URC/LRE/LRC) systems (outdoor unit display)) The evaporator coil temperature is too high and the unit has stopped to protect itself. Fault – service needed
J1 (Cascade (URC/CRE), UltraSlim (URC/LRE) and UltraSlim R-32 (URC/LRE/LRC) systems (outdoor unit display)) The condenser coil temperature is too high and the unit has stopped to protect itself. Fault – service needed
J2 (Cascade (URC/CRE), UltraSlim (URC/LRE) and UltraSlim R-32 (URC/LRE/LRC) systems (outdoor unit display)) The compressor discharge temperature is too high and the unit has stopped to protect itself. Fault – service needed
J3 (Cascade (URC/CRE), UltraSlim (URC/LRE) and UltraSlim R-32 (URC/LRE/LRC) systems (outdoor unit display)) The power factor correction (PFC) module in the outdoor unit has tripped a protection. Fault – service needed
J4 (Cascade (URC/CRE), UltraSlim (URC/LRE) and UltraSlim R-32 (URC/LRE/LRC) systems (outdoor unit display)) The outdoor unit’s main board has lost communication with the compressor drive board. Fault – service needed
J5 (Cascade (URC/CRE), UltraSlim (URC/LRE) and UltraSlim R-32 (URC/LRE/LRC) systems (outdoor unit display)) The high pressure protection has tripped, usually because the outdoor unit cannot get rid of heat. Fault – service needed
J6 (Cascade (URC/CRE), UltraSlim (URC/LRE) and UltraSlim R-32 (URC/LRE/LRC) systems (outdoor unit display)) The low pressure protection has tripped, usually because the system is low on refrigerant. Fault – service needed
J8 (Cascade (URC/CRE), UltraSlim (URC/LRE) and UltraSlim R-32 (URC/LRE/LRC) systems (outdoor unit display)) The incoming AC power voltage is outside safe limits and the unit has stopped. Fault – service needed
LP (UltraSlim R-32 (URC/LRE/LRC) systems (outdoor unit display)) The unit has stopped because the outdoor temperature is too low for safe operation. Normal operation
P0 (Aurora (SWB) and Serene (WRC/WRE) wall splits, Cascade (URC/CRE) and UltraSlim (URC/LRE) split ducted and cassette systems (indoor and outdoor displays, including the UltraSlim R-32 outdoor display) and multi-split indoor units (MRE/BRE) (1 lamp flash))
also shown as 1 lamp flash
The inverter power module (IPM) has detected a fault or excessive current and shut the compressor down. Fault – service needed
P0 (Systems with the WC-02 wired wall controller (Cascade and UltraSlim ducted and cassette units)) The evaporator (indoor coil) temperature protection has tripped. Minor fault
P1 (Aurora (SWB) and Serene (WRC/WRE) wall splits, Cascade (URC/CRE) and UltraSlim (URC/LRE) split ducted and cassette systems (indoor and outdoor displays, including the UltraSlim R-32 outdoor display) and multi-split indoor units (MRE/BRE) (2 lamp flashes))
also shown as 2 lamp flashes
The supply voltage to the unit is too high or too low. Fault – service needed
P1 (Multi-split outdoor units (MRC): models MRC-100AS-4, MRC-110AS-5 and MRC-135AS-5 only) The high pressure protection has tripped, usually because the outdoor unit cannot get rid of heat. Fault – service needed
P1 (Systems with the WC-02 wired wall controller (Cascade and UltraSlim ducted and cassette units)) The unit is in defrost or anti-cold-draught mode, which is normal operation rather than a fault. Normal operation
P2 (Aurora (SWB) and Serene (WRC/WRE) wall splits (Aurora SWB52C and SWB70C only), Cascade (URC/CRE) and UltraSlim (URC/LRE) split ducted and cassette systems and the UltraSlim R-32 outdoor display (3 lamp flashes))
also shown as 3 lamp flashes
The compressor (or on some models the inverter module) has overheated and the unit has shut down to protect it. Fault – service needed
P2 (Multi-split outdoor units (MRC): models MRC-100AS-4, MRC-110AS-5 and MRC-135AS-5 only) The low pressure protection has tripped, usually because the system is low on refrigerant. Fault – service needed
P2 (Systems with the WC-02 wired wall controller (Cascade and UltraSlim ducted and cassette units)) The condenser temperature protection has tripped. Fault – service needed
P3 (Cascade (URC/CRE) and UltraSlim (URC/LRE) split ducted and cassette systems (indoor and outdoor displays, 4 lamp flashes))
also shown as 4 lamp flashes
The unit has stopped because the outdoor temperature is too low for safe operation. Normal operation
P3 (Multi-split outdoor units (MRC)) The outdoor unit is drawing too much electrical current and has shut down to protect itself. Urgent – turn it off
P3 (Systems with the WC-02 wired wall controller (Cascade and UltraSlim ducted and cassette units)) The compressor temperature protection has tripped. Fault – service needed
P4 (Aurora (SWB) and Serene (WRC/WRE) wall splits, Cascade (URC/CRE) and UltraSlim (URC/LRE) split ducted and cassette systems (indoor and outdoor displays, including compressor rotor position protection, and the UltraSlim R-32 outdoor display) and multi-split indoor units (MRE/BRE) (5 lamp flashes))
also shown as 5 lamp flashes
The inverter compressor drive has reported an error and stopped the compressor. Fault – service needed
P4 (Multi-split outdoor units (MRC); also shown as P4 (discharge pipe temperature protection) on the WC-02 wired controller) The compressor discharge temperature is too high and the unit has stopped to protect the compressor. Fault – service needed
P5 (Multi-split systems (MRE/BRE indoor units, 6 lamp flashes))
also shown as 6 lamp flashes
Two indoor units are asking for opposite modes (one heating, one cooling), which the system cannot do at the same time. Normal operation
P5 (Multi-split outdoor units (MRC)) The condenser temperature is too high and the unit has stopped to protect itself. Fault – service needed
P5 (Systems with the WC-02 wired wall controller (Cascade and UltraSlim ducted and cassette units)) The discharge high pressure protection has tripped. Fault – service needed
P6 (Multi-split systems (MRE/BRE indoor units, 7 lamp flashes))
also shown as 7 lamp flashes
The outdoor unit has tripped on a high or low refrigerant pressure fault (the outdoor display shows J5 for high pressure or J6 for low pressure). Fault – service needed
P6 (Cascade (URC/CRE) and UltraSlim (URC/LRE) split ducted and cassette systems (indoor display, 7 lamp flashes))
also shown as 7 lamp flashes
The compressor voltage protection has tripped. Fault – service needed
P6 (Multi-split outdoor units (MRC)) The inverter power module (IPM) has tripped a protection and stopped the compressor. Fault – service needed
P6 (Systems with the WC-02 wired wall controller (Cascade and UltraSlim ducted and cassette units)) The discharge low pressure protection has tripped, usually because the system is low on refrigerant. Fault – service needed
P7 (Cascade (URC/CRE) and UltraSlim (URC/LRE) split ducted and cassette systems (indoor and outdoor displays, 8 lamp flashes) and the UltraSlim R-32 outdoor display)
also shown as 8 lamp flashes
The outdoor inverter (IGBT) temperature sensor is faulty (open or short circuit). Minor fault
P7 (Systems with the WC-02 wired wall controller (Cascade and UltraSlim ducted and cassette units)) The over-voltage protection has tripped. Fault – service needed
P8 (Systems with the WC-02 wired wall controller (Cascade and UltraSlim ducted and cassette units)) The compressor overload protection has tripped. Fault – service needed
PC00 (Cascade R-32 (URC/CRC) and UltraSlim R-32 (URC/LRE/LRC) systems; Serene Series 2 R-32 wall splits show the same codes)
also shown as 7 lamp flashes
The inverter power module has detected a fault or excessive current and shut the compressor down. Fault – service needed
PC01 (Cascade R-32 (URC/CRC) and UltraSlim R-32 (URC/LRE/LRC) systems; Serene Series 2 R-32 wall splits show the same codes)
also shown as 2 lamp flashes
The supply voltage to the unit is too high or too low. Fault – service needed
PC02 (Cascade R-32 (URC/CRC) and UltraSlim R-32 (URC/LRE/LRC) systems; Serene Series 2 R-32 wall splits show the same codes)
also shown as 3 lamp flashes
The compressor or inverter module has overheated and the unit has shut down to protect itself. Fault – service needed
PC03 (Cascade R-32 (URC/CRC) and UltraSlim R-32 (URC/LRE/LRC) systems; Serene Series 2 R-32 wall splits show the same codes)
also shown as 7 lamp flashes
The system has tripped on a high or low refrigerant pressure fault (some models). Fault – service needed
PC04 (Cascade R-32 (URC/CRC) and UltraSlim R-32 (URC/LRE/LRC) systems; Serene Series 2 R-32 wall splits show the same codes)
also shown as 5 lamp flashes
The inverter compressor drive has reported an error and stopped the compressor. Fault – service needed
PF (Systems with the WC-02 wired wall controller (Cascade and UltraSlim ducted and cassette units)) A fault has occurred elsewhere in the system; check the indoor or outdoor unit display for the detailed code. Minor fault
dF (Serene Series 2 wall split indoor units (also shown as dEF on ducted outdoor displays)) The unit is running a normal defrost cycle in heating mode, not a fault. Normal operation

Codes that mean switch the system off

If your ActronAir unit shows EC, F0, P3, EL0C, E60, E74, E74, E79, turn the system off at the isolator and leave it off. These faults involve the compressor, refrigerant or electrical protection, and running the unit can cause further damage.

The most serious ActronAir fault codes explained

What does ActronAir fault code EC mean? (Aurora (SWB) and Serene (WRC/WRE) wall splits and Cascade (URC/CRE) and UltraSlim (URC/LRE) split ducted and cassette systems (7 lamp flashes))

The system has detected a possible refrigerant leak.

Likely causes:

  • Refrigerant leak in the piping or coils
  • Faulty leak detection sensor

Safe checks before you call:

  • Stop using the unit and switch it off at the isolator or breaker
  • Open windows to ventilate the room
  • Do not use open flames near the indoor unit

What does ActronAir fault code F0 mean? (Serene (WRC/WRE) wall splits and Cascade (URC/CRE) and UltraSlim (URC/LRE) split ducted and cassette systems (some units, 1 lamp flash); also the outdoor display on Cascade, UltraSlim and UltraSlim R-32 systems)

Overcurrent or overload protection has tripped.

Likely causes:

  • Power surge or unstable supply voltage
  • Compressor or fan motor drawing excess current
  • Electrical fault on the outdoor unit

Safe checks before you call:

  • Turn the system off at the isolator for 5 minutes, then restart it once. If F0 returns, leave the system off.

What does ActronAir fault code P3 mean? (Multi-split outdoor units (MRC))

The outdoor unit is drawing too much electrical current and has shut down to protect itself.

Likely causes:

  • Compressor working too hard due to blocked airflow
  • Power supply problem
  • Failing compressor

Safe checks before you call:

  • Look at the outdoor unit and make sure leaves, grass or objects are not blocking the airflow (do not open the unit)
  • Clean or check the return air filter is not clogged
  • Turn the system off at the isolator or breaker, wait 5 minutes, then restart it

What does ActronAir fault code EL0C mean? (Cascade R-32 (URC/CRC) and UltraSlim R-32 (URC/LRE/LRC) systems; Serene Series 2 R-32 wall splits show the same codes)

The system has detected a possible refrigerant leak (some models).

Likely causes:

  • Refrigerant leak in the piping or coils
  • Faulty leak detection sensor

Safe checks before you call:

  • Stop using the unit and switch it off at the isolator or breaker
  • Open windows to ventilate the room
  • Do not use open flames near the indoor unit

What does ActronAir fault code E60 mean? (Advance, Aires and QUE three phase ducted systems)

The compressor drive has detected excessive current in a compressor phase and shut down.

Likely causes:

  • Compressor winding or wiring fault
  • Compressor drive fault
  • Compressor working too hard due to blocked airflow

Safe checks before you call:

  • Look at the outdoor unit and make sure leaves, grass or objects are not blocking the airflow (do not open the unit)
  • Clean or check the return air filter is not clogged
  • Turn the system off at the isolator or breaker, wait 5 minutes, then restart it

What does ActronAir fault code E74 mean? (Advance and Aires ducted systems)

The drive has tripped on IGBT overcurrent, which can point to a choke wiring problem or failure.

Likely causes:

  • Choke wiring problem or choke failure
  • Drive power electronics fault
  • Compressor winding fault

Safe checks before you call:

  • Turn the system off at the isolator or breaker, wait 5 minutes, then restart it

What does ActronAir fault code E79 mean? (Advance and Aires ducted systems)

The drive has tripped a hardware overcurrent (IPM) protection on the compressor.

Likely causes:

  • Drive power electronics fault
  • Compressor winding fault
  • Failing compressor

Safe checks before you call:

  • Turn the system off at the isolator or breaker, wait 5 minutes, then restart it

What does ActronAir fault code E0 mean? (Aurora (SWB) and Serene (WRC/WRE) wall splits, Cascade (URC/CRE) and UltraSlim (URC/LRE) split ducted and cassette systems and multi-split indoor units (MRE/BRE) (1 lamp flash))

The indoor unit’s memory chip (EEPROM) has a parameter error.

Likely causes:

  • Corrupted indoor board memory
  • Indoor control board fault

Safe checks before you call:

  • Turn the system off at the isolator or breaker, wait 5 minutes, then restart it

What does ActronAir fault code E1 mean? (Aurora (SWB) and Serene (WRC/WRE) wall splits, Cascade (URC/CRE) and UltraSlim (URC/LRE) split ducted and cassette systems (indoor and outdoor displays, including the UltraSlim R-32 outdoor display), multi-split indoor units (MRE/BRE) (2 lamp flashes) and the WC-02 wired controller)

The indoor and outdoor units have lost communication with each other.

Likely causes:

  • Damaged or loose interconnecting cable
  • Power interruption to the outdoor unit
  • Indoor or outdoor board fault

Safe checks before you call:

  • Check the outdoor unit isolator switch (next to the outdoor unit) is switched on
  • Turn the system off at the isolator or breaker, wait 5 minutes, then restart it

What does ActronAir fault code E3 mean? (Aurora (SWB) and Serene (WRC/WRE) wall splits, Cascade (URC/CRE) and UltraSlim (URC/LRE) split ducted and cassette systems and multi-split indoor units (MRE/BRE) (4 lamp flashes))

The indoor fan is not running at the correct speed.

Likely causes:

  • Faulty indoor fan motor
  • Fan obstruction
  • Indoor control board fault

Safe checks before you call:

  • Clean or check the return air filter is not clogged
  • Turn the system off at the isolator or breaker, wait 5 minutes, then restart it

What does ActronAir fault code E8 mean? (Cascade (URC/CRE) and UltraSlim (URC/LRE) twin systems (indoor display, 9 lamp flashes))

The master and slave indoor units of a twin system have lost communication with each other.

Likely causes:

  • Interconnecting cable fault between the twin indoor units
  • Indoor PCB fault

Safe checks before you call:

  • Turn the system off at the isolator or breaker, wait 5 minutes, then restart it

What does ActronAir fault code E9 mean? (Cascade (URC/CRE) and UltraSlim (URC/LRE) twin systems (indoor display, 10 lamp flashes))

Another indoor unit in the twin system has a fault.

Likely causes:

  • A fault on the other indoor unit of the twin pair
  • Communication fault between the twin units

Safe checks before you call:

  • Check the other indoor unit’s display for its own fault code and look that code up

Fault confirmed? Here is what to do next

A fault code is the starting point, not the fix. Start here:

Call us on 08 8296 7888 or book online and we will call or text you back ASAP.

Sources for this page

Every ActronAir code above is checked against these Australian documents. Open them yourself to verify anything on this page:

ActronAir fault code FAQs

Where do I find the fault code on a ActronAir air conditioner?

Check the remote or wall controller display first. Some models flash the indoor unit’s lamps in a pattern instead; the table above lists documented lamp patterns alongside their codes. If nothing is showing, the code may only appear while the fault is active.

Can I clear a ActronAir fault code myself?

You can reset the system by turning it off at the isolator or breaker for five minutes. If the code stays gone, it was a one-off. If it returns, the fault is real and needs a licensed technician, and repeated resets can cause further damage on compressor or refrigerant faults.

Does a ActronAir fault code mean I need a new air conditioner?

Usually not. Most codes point to repairable faults like sensors, fan motors or drainage. Our fault find gives you an honest verdict either way, and the fee is credited if you repair with us.

Are these ActronAir fault codes correct for Australian models?

Yes. Every code on this page was checked against Australian documentation (docs.actronair.com.au, actronair.com.au, valleyairconditioning.com.au), not overseas lists, because the same code can mean different things in different markets. Meanings still vary between model series, so treat this page as reference and cross-check your unit’s manual.

Written by Oliver Hastings, T&K Airpower. Last updated 01/08/2026. Compiled from Australian sources including docs.actronair.com.au, actronair.com.au, valleyairconditioning.com.au, airconditioningmackay.com.au, so you can check every code against the official documentation. Fault code meanings vary between model series and controllers, so treat this page as reference only and never remove panels or work on the refrigeration or electrical parts of the system yourself.

T&K Airpower - Air Conditioner and Electrician Repair experts in Adelaide

Established, Local, and Accountable

We’ve been working in Adelaide homes for over 30 years.

Every job is done by our own technicians, employed, not subcontracted, so the person on your roof or at your switchboard is accountable for the work. We back it with a lifetime workmanship warranty, and we’ll be here to stand behind it long after the job is done.

null

With Over 30 Years of Experience, You Can Trust Our Certified Technicians To Do The Job Right The FIRST TIME for your air conditioner and electrician needs.

null

Honest Advice on Your Home's Comfort, Energy and Safety

Every price and answer on this page comes from the same pricing and diagnostics our own technicians use, so what you see is a genuine indication, not a teaser.

Where an upgrade is genuinely needed, we’ll explain why in plain terms and set out your best option. No pressure, no unnecessary work.

We only recommend it when it improves safety, reliability or long-term performance.

We’ll call or text you back ASAP!

Bright green logo with sunburst design

Service Area

null

Servicing Adelaide Homes and Surrounding Suburbs

We provide residential electrical energy solutions and upgrades across metropolitan Adelaide, including inner eastern, western and southern suburbs