What does your Fujitsu General fault code mean?

Pick the code showing on your remote, wall controller or indoor unit and see what it means, what commonly causes it, and what is safe to check yourself. This page covers 67 Fujitsu General fault codes for units sold in Australia, compiled from official Australian manufacturer and distributor documentation, the same references our own technicians carry.

Heads up: Fujitsu General uses the same code with different meanings on different product ranges, so check the model range shown next to the code.

Every Fujitsu General fault code at a glance

Some models show faults as a flashing-light pattern instead of a code; documented lamp patterns are listed alongside their codes.

Code What it means Severity
00 (Older ducted, cassette and floor console systems (ARTA, AUTA, ABTA and similar series)) The wired wall controller cannot communicate with the indoor unit. Fault – service needed
01 (Older ducted, cassette and floor console systems (ARTA, AUTA, ABTA and similar series))
also shown as 26, 27
A communication fault inside the system, between the indoor and outdoor units or between the indoor unit’s own circuit boards. Fault – service needed
02 (Older ducted, cassette and floor console systems (ARTA, AUTA, ABTA and similar series); the short circuit variant 03 is documented for the older ART ducted systems (ART-LUAD and ART-LUAK series))
also shown as 03
The sensor that reads the room air temperature has failed (code 02 is an open circuit; on older ART ducted systems code 03 indicates the same sensor short circuited). Fault – service needed
04 (Older ducted, cassette and floor console systems (ARTA, AUTA, ABTA and similar series); the short circuit variant 05 is documented for the older ART ducted systems (ART-LUAD and ART-LUAK series))
also shown as 05
The temperature sensor in the middle of the indoor coil has failed (code 04 is an open circuit; on older ART ducted systems code 05 indicates the same sensor short circuited). Fault – service needed
06 (Older ducted, cassette and floor console systems (ARTA, AUTA, ABTA and similar series); the short circuit variant 07 is documented for the older ART ducted systems (ART-LUAD and ART-LUAK series))
also shown as 07
The temperature sensor at the outlet of the outdoor coil has failed (code 06 is an open circuit; on older ART ducted systems code 07 indicates the same sensor short circuited). Fault – service needed
08 (Older ART ducted systems (ART-LUAD and ART-LUAK series)) The power supply to the unit is connected incorrectly, such as a missing or wrongly wired phase. Fault – service needed
09 (Older ducted, cassette and floor console systems (ARTA, AUTA, ABTA and similar series); on J Series multi systems E:09 instead means a room temperature sensor fault)
also shown as E:09
The float switch has tripped because condensate water is not draining away. Fault – service needed
0A (Older ducted, cassette and floor console systems (ARTA, AUTA, ABTA and similar series); the short circuit variant 0b is documented for the older ART ducted systems (ART-LUAD and ART-LUAK series))
also shown as 0b
The sensor that reads the outside air temperature has failed (code 0A is an open circuit; on older ART ducted systems code 0b indicates the same sensor short circuited). Fault – service needed
0C (Older ducted, cassette and floor console systems (ARTA, AUTA, ABTA and similar series); the short circuit variant 0d is documented for the older ART ducted systems (ART-LUAD and ART-LUAK series))
also shown as 0d
The temperature sensor on the compressor discharge pipe has failed (code 0C is an open circuit; on older ART ducted systems code 0d indicates the same sensor short circuited). Fault – service needed
0F (Older ducted, cassette and floor console systems (ARTA, AUTA, ABTA and similar series)) The compressor discharge temperature climbed too high, which can mean the system is low on refrigerant. Fault – service needed
11 (Current splits, ducted, multi-head and cassette systems (varies by series); on older ducted systems (ART-LUAD/LUAK, ABTF and ARTC72/90 series) 11 instead means a model information error, and on J Series multi systems E:11 means a drain fault)
also shown as E:11, Operation LED 1 flash + Timer LED 1 flash, Economy LED continuous flash
The indoor and outdoor units have stopped communicating with each other. Fault – service needed
12 (Current splits, ducted, multi-head and cassette systems with a wired wall controller)
also shown as E:12, Operation LED 1 flash + Timer LED 2 flashes, Economy LED continuous flash
The wired wall controller has lost communication with the indoor unit. Fault – service needed
15 (Current splits, multi-head and cassette systems (cassette confirmed on AUTG54LRLA; varies by series))
also shown as Operation LED 1 flash + Timer LED 5 flashes, Economy LED continuous flash
The installer’s commissioning test run was never completed, so the system will not run normally. Minor fault
21 (Multi-head systems, branch-box setups and simultaneous-multi cassettes (AUTG54LRLA and similar); on J Series multi systems E:21 instead means a parallel communication error)
also shown as Operation LED 2 flashes + Timer LED 1 flash, Economy LED continuous flash
The wiring and pipework between the units does not match what the system expects. Fault – service needed
22 (Current splits, ducted, multi-head and cassette systems (varies by series); older AWT wall splits (AWT14/17LSAZ) use the same number for a different fault)
also shown as E:22, Operation LED 2 flashes + Timer LED 2 flashes, Economy LED continuous flash
The connected indoor unit’s capacity does not match what the outdoor unit expects. Fault – service needed
23 (Multi-head systems; older AWT wall splits (AWT14/17LSAZ) use the same number for a different fault)
also shown as Operation LED 2 flashes + Timer LED 3 flashes, Economy LED continuous flash
The combination of indoor units connected is not one the outdoor unit supports. Fault – service needed
24 (Multi-head systems and branch-box setups; older AWT wall splits (AWT14/17LSAZ) use the same number for a different fault)
also shown as Operation LED 2 flashes + Timer LED 4 flashes, Economy LED continuous flash
The system has detected the wrong number of indoor units or branch boxes connected. Fault – service needed
27 (Current simultaneous-multi cassette and ducted systems (AUTG54LRLA and similar); on older ARTA/AUTA/ABTA systems 27 instead indicates an indoor signal (display PCB) communication error – see code 01)
also shown as E:27, Operation LED 2 flashes + Timer LED 7 flashes, Economy LED continuous flash
The master and slave unit set-up of a simultaneous multi system is wrong or has been lost. Fault – service needed
28 (Older ducted, cassette and floor console systems (ARTA, AUTA, ABTA and similar series)) The temperature sensor at the inlet of the indoor coil has failed. Fault – service needed
31 (Ducted systems (ARTG series) and larger wall splits (ASTG34LFCA and similar); on older three phase ducted and cassette systems (ARTC-LCTU, AUTA54LCLU) 31 instead means a master and slave unit set-up error)
also shown as E:31, Operation LED 3 flashes + Timer LED 1 flash, Economy LED continuous flash
Power to the system was interrupted while it was running. Minor fault
32 (Current splits, ducted, multi-head and cassette systems (varies by series); on older three phase ducted systems (ARTC-LCTU, AUTA54LCLU) 32 instead means an indoor unit number set-up error, and on J Series multi systems E:32 means an outdoor unit fault; older AWT wall splits (AWT14/17LSAZ) use the same number for a different fault)
also shown as E:32, Operation LED 3 flashes + Timer LED 2 flashes, Economy LED continuous flash
The main circuit board inside the indoor unit has failed or lost its stored settings. Fault – service needed
35 (Current splits, ducted, multi-head and cassette systems (varies by series); older AWT wall splits (AWT14/17LSAZ) use the same number for a different fault)
also shown as E:35, Operation LED 3 flashes + Timer LED 5 flashes, Economy LED continuous flash
The manual auto button on the indoor unit is stuck or faulty. Minor fault
39 (Ducted systems (ARTG series) and larger wall splits (ASTG34LFCA and similar))
also shown as E:39, Operation LED 3 flashes + Timer LED 9 flashes, Economy LED continuous flash
The circuit that drives the indoor fan motor has failed. Fault – service needed
41 (Current splits, ducted, multi-head and cassette systems (varies by series))
also shown as E:41, Operation LED 4 flashes + Timer LED 1 flash, Economy LED continuous flash
The sensor that reads the room air temperature has failed. Fault – service needed
42 (Current splits, ducted, multi-head and cassette systems (varies by series); older AWT wall splits (AWT14/17LSAZ) use the same number for a different fault)
also shown as E:42, Operation LED 4 flashes + Timer LED 2 flashes, Economy LED continuous flash
The temperature sensor on the indoor coil (heat exchanger) has failed. Fault – service needed
51 (Current splits, ducted, multi-head and cassette systems (varies by series))
also shown as E:51, Operation LED 5 flashes + Timer LED 1 flash, Economy LED continuous flash
The indoor fan motor has failed or cannot spin properly. Fault – service needed
53 (Current splits, ducted, multi-head and cassette systems (varies by series); older AWT wall splits (AWT14/17LSAZ) use the same number for a different fault)
also shown as E:53, Operation LED 5 flashes + Timer LED 3 flashes, Economy LED continuous flash
The system has detected a condensate drainage problem, usually water not draining away. Fault – service needed
57 (Cassette and ducted systems with motorised dampers (varies by series); older AWT wall splits (AWT14/17LSAZ) instead use 57 for a fan communication fault)
also shown as E:57, Operation LED 5 flashes + Timer LED 7 flashes, Economy LED continuous flash
A damper inside the indoor unit is not moving correctly. Minor fault
59 (Ducted systems (ARTG series) and larger wall splits (ASTG34LFCA and similar))
also shown as E:59, Operation LED 5 flashes + Timer LED 9 flashes, Economy LED continuous flash
The second indoor fan motor in the ducted unit has failed. Fault – service needed
5U (Ducted systems (ARTG series) and larger wall splits (ASTG34LFCA and similar))
also shown as E:5U, Operation LED 5 flashes + Timer LED 15 flashes, Economy LED continuous flash
The indoor unit has reported a general fault. Fault – service needed
62 (Current splits, ducted, multi-head and cassette systems (varies by series); older AWT wall splits (AWT14/17LSAZ) use the same number for a different fault)
also shown as E:62, Operation LED 6 flashes + Timer LED 2 flashes, Economy LED continuous flash
The main circuit board in the outdoor unit has failed or has the wrong model information stored. Fault – service needed
63 (Current splits, ducted, multi-head and cassette systems (varies by series); older AWT wall splits (AWT14/17LSAZ) use the same number for a different fault)
also shown as E:63, Operation LED 6 flashes + Timer LED 3 flashes, Economy LED continuous flash
The inverter, which controls the compressor speed, has failed in the outdoor unit. Fault – service needed
64 (Current splits, ducted, multi-head and cassette systems (varies by series))
also shown as E:64, Operation LED 6 flashes + Timer LED 4 flashes, Economy LED continuous flash
The active filter or PFC power circuit in the outdoor unit has failed. Fault – service needed
65 (Current splits, ducted, multi-head and cassette systems (varies by series))
also shown as E:65, Operation LED 6 flashes + Timer LED 5 flashes, Economy LED continuous flash
The IPM, the power module that drives the compressor, has reported a fault. Fault – service needed
6A (Current cassette and ducted systems with wired controllers (varies by series))
also shown as E:6A, Operation LED 6 flashes + Timer LED 10 flashes, Economy LED continuous flash
The display panel and the main circuit board inside the indoor unit have stopped talking to each other. Fault – service needed
71 (Current splits, ducted, multi-head and cassette systems (varies by series))
also shown as E:71, Operation LED 7 flashes + Timer LED 1 flash, Economy LED continuous flash
The temperature sensor on the compressor discharge pipe has failed. Fault – service needed
72 (Current splits, ducted, multi-head and cassette systems (varies by series); older AWT wall splits (AWT14/17LSAZ) use the same number for a different fault)
also shown as E:72, Operation LED 7 flashes + Timer LED 2 flashes, Economy LED continuous flash
The temperature sensor on the compressor body has failed. Fault – service needed
73 (Current splits, ducted, multi-head and cassette systems (varies by series); older AWT wall splits (AWT14/17LSAZ) use the same number for a different fault)
also shown as E:73, Operation LED 7 flashes + Timer LED 3 flashes, Economy LED continuous flash
A temperature sensor on the outdoor coil (heat exchanger) has failed. Fault – service needed
74 (Current splits, ducted, multi-head and cassette systems (varies by series); older AWT wall splits (AWT14/17LSAZ) use the same number for a different fault)
also shown as E:74, Operation LED 7 flashes + Timer LED 4 flashes, Economy LED continuous flash
The sensor that reads the outside air temperature has failed. Fault – service needed
75 (Current splits, ducted, multi-head and cassette systems (varies by series); older AWT wall splits (AWT14/17LSAZ) use the same number for a different fault)
also shown as E:75, Operation LED 7 flashes + Timer LED 5 flashes, Economy LED continuous flash
The temperature sensor on the suction gas pipe has failed. Fault – service needed
76 (Current splits, ducted, multi-head and cassette systems (varies by series))
also shown as E:76, Operation LED 7 flashes + Timer LED 6 flashes, Economy LED continuous flash
A temperature sensor on a refrigerant valve in the outdoor unit has failed. Fault – service needed
77 (Current splits, ducted, multi-head and cassette systems (varies by series))
also shown as E:77, Operation LED 7 flashes + Timer LED 7 flashes, Economy LED continuous flash
The temperature sensor on the outdoor unit’s heat sink has failed. Fault – service needed
82 (Larger wall splits (ASTG24, ASTG34 and similar series) and cassettes (AUTG54LRLA); older AWT wall splits (AWT14/17LSAZ) use the same number for a different fault)
also shown as E:82, Operation LED 8 flashes + Timer LED 2 flashes, Economy LED continuous flash
A temperature sensor on the sub-cool heat exchanger gas pipe has failed. Fault – service needed
83 (Larger wall splits (ASTG24, ASTG34 and similar series) and cassettes (AUTG54LRLA); older AWT wall splits (AWT14/17LSAZ) use the same number for a different fault)
also shown as E:83, Operation LED 8 flashes + Timer LED 3 flashes, Economy LED continuous flash
The temperature sensor on the liquid refrigerant pipe has failed. Fault – service needed
84 (Current splits, ducted, multi-head and cassette systems (varies by series))
also shown as E:84, Operation LED 8 flashes + Timer LED 4 flashes, Economy LED continuous flash
The sensor that measures how much current the compressor is drawing has failed. Fault – service needed
86 (Current splits, ducted, multi-head and cassette systems (varies by series))
also shown as E:86, Operation LED 8 flashes + Timer LED 6 flashes, Economy LED continuous flash
A refrigerant pressure sensor or the high pressure safety switch has reported a fault. Fault – service needed
94 (Current splits, ducted, multi-head and cassette systems (varies by series))
also shown as E:94, Operation LED 9 flashes + Timer LED 4 flashes, Economy LED continuous flash
The outdoor unit shut down after detecting too much electrical current. Fault – service needed
95 (Current splits, ducted, multi-head and cassette systems (varies by series))
also shown as E:95, Operation LED 9 flashes + Timer LED 5 flashes, Economy LED continuous flash
The compressor motor could not start or run correctly, so the system shut down. Fault – service needed
97 (Current splits, ducted, multi-head and cassette systems (varies by series))
also shown as E:97, Operation LED 9 flashes + Timer LED 7 flashes, Economy LED continuous flash
The outdoor fan motor has failed or cannot spin properly. Fault – service needed
98 (Ducted systems (ARTG series) and larger wall splits (ASTG34LFCA and similar))
also shown as E:98, Operation LED 9 flashes + Timer LED 8 flashes, Economy LED continuous flash
The second outdoor fan motor has failed or cannot spin properly. Fault – service needed
99 (Current splits, ducted, multi-head and cassette systems (varies by series))
also shown as E:99, Operation LED 9 flashes + Timer LED 9 flashes, Economy LED continuous flash
The 4-way valve, which switches the system between heating and cooling, is not working correctly. Fault – service needed
9A (Current cassette and ducted systems with wired controllers (varies by series))
also shown as E:9A, Operation LED 9 flashes + Timer LED 10 flashes, Economy LED continuous flash
The electronic expansion valve coil in the outdoor unit is faulty or disconnected. Fault – service needed
A1 (Current splits, ducted, multi-head and cassette systems (varies by series))
also shown as E:A1, Operation LED 10 flashes + Timer LED 1 flash, Economy LED continuous flash
The compressor discharge temperature climbed too high, so the system shut down to protect itself. Fault – service needed
A3 (Current splits, ducted, multi-head and cassette systems (varies by series))
also shown as E:A3, Operation LED 10 flashes + Timer LED 3 flashes, Economy LED continuous flash
The compressor body temperature climbed too high, so the system shut down to protect itself. Fault – service needed
A4 (Current cassette and ducted systems with wired controllers (varies by series))
also shown as E:A4, Operation LED 10 flashes + Timer LED 4 flashes, Economy LED continuous flash
Refrigerant pressure on the high side climbed too far, so the system shut down to protect itself. Fault – service needed
A5 (Current splits, ducted, multi-head and cassette systems (varies by series))
also shown as E:A5, Operation LED 10 flashes + Timer LED 5 flashes, Economy LED continuous flash
Refrigerant pressure on the low side has dropped too far, often a sign of a gas leak. Fault – service needed
E0:00 (Older systems with hardwired wall controllers) The wall controller has lost communication with the indoor unit. Fault – service needed
E1:00 (Older systems with hardwired wall controllers) The indoor and outdoor units have stopped communicating with each other. Fault – service needed
E2:00 (Older systems with hardwired wall controllers)
also shown as E3:00
The return air temperature sensor is not reading correctly (E2:00 open circuit, E3:00 short circuit). Fault – service needed
E4:00 (Older systems with hardwired wall controllers)
also shown as E5:00
The indoor coil temperature sensor has failed (E4:00 open circuit, E5:00 short circuit). Fault – service needed
E6:00 (Older systems with hardwired wall controllers)
also shown as E7:00
The outdoor coil temperature sensor has failed (E6:00 open circuit, E7:00 short circuit). Fault – service needed
EA:00 (Older systems with hardwired wall controllers)
also shown as Eb:00, EB:00
The outdoor air temperature sensor has failed (EA:00 open circuit, Eb:00 short circuit). Fault – service needed
EC:00 (Older systems with hardwired wall controllers)
also shown as Ec:00, Ed:00, ED:00
The discharge pipe temperature sensor has failed (Ec:00 open circuit, Ed:00 short circuit). Fault – service needed
EE:00 (Older systems with hardwired wall controllers) The system shut down on a high refrigerant pressure problem. Fault – service needed
EE:EE (Systems with wired wall controllers (splits, ducted, multi-head, cassette))
also shown as E:EE, EE
The system has locked out because it detected a fault; the controller is holding the actual error code in memory for a technician to retrieve. Fault – service needed
EF:00 (Older systems with hardwired wall controllers) The discharge pipe temperature climbed too high, which often means the system is short of refrigerant gas. Fault – service needed
J2 (Multi-head systems with branch boxes (Flexible Multi))
also shown as E:J2, Operation LED 13 flashes + Timer LED 2 flashes, Economy LED continuous flash
A branch box in the multi-head system has a fault or has stopped communicating. Fault – service needed

The most serious Fujitsu General fault codes explained

What does Fujitsu General fault code 11 mean? (Current splits, ducted, multi-head and cassette systems (varies by series); on older ducted systems (ART-LUAD/LUAK, ABTF and ARTC72/90 series) 11 instead means a model information error, and on J Series multi systems E:11 means a drain fault)

The indoor and outdoor units have stopped communicating with each other.

Likely causes:

  • Damaged or loose interconnecting cable between indoor and outdoor units
  • Power interruption or surge damage to a circuit board
  • Indoor or outdoor unit PCB failure

Safe checks before you call:

  • Check the outdoor unit isolator switch is on
  • Turn the system off at the isolator or breaker for 5 to 10 minutes, then restart

What does Fujitsu General fault code 12 mean? (Current splits, ducted, multi-head and cassette systems with a wired wall controller)

The wired wall controller has lost communication with the indoor unit.

Likely causes:

  • Loose or damaged controller cable
  • Wall controller fault
  • Indoor unit PCB fault

Safe checks before you call:

  • Turn the system off at the isolator or breaker for 5 to 10 minutes, then restart

What does Fujitsu General fault code 21 mean? (Multi-head systems, branch-box setups and simultaneous-multi cassettes (AUTG54LRLA and similar); on J Series multi systems E:21 instead means a parallel communication error)

The wiring and pipework between the units does not match what the system expects.

Likely causes:

  • Interconnecting wiring and refrigerant pipes crossed between rooms during installation
  • Wiring altered after installation
  • Unit number or refrigerant circuit address setting error on simultaneous multi systems

Safe checks before you call:

  • Turn the system off at the isolator or breaker for 5 to 10 minutes, then restart

What does Fujitsu General fault code 22 mean? (Current splits, ducted, multi-head and cassette systems (varies by series); older AWT wall splits (AWT14/17LSAZ) use the same number for a different fault)

The connected indoor unit’s capacity does not match what the outdoor unit expects.

Likely causes:

  • Mismatched indoor and outdoor unit pairing
  • Indoor unit PCB fault or wrong model information

Safe checks before you call:

  • Turn the system off at the isolator or breaker for 5 to 10 minutes, then restart

What does Fujitsu General fault code 23 mean? (Multi-head systems; older AWT wall splits (AWT14/17LSAZ) use the same number for a different fault)

The combination of indoor units connected is not one the outdoor unit supports.

Likely causes:

  • Unsupported mix of indoor unit sizes on a multi-head outdoor unit
  • Indoor unit swapped for an incompatible model

Safe checks before you call:

  • Turn the system off at the isolator or breaker for 5 to 10 minutes, then restart

What does Fujitsu General fault code 24 mean? (Multi-head systems and branch-box setups; older AWT wall splits (AWT14/17LSAZ) use the same number for a different fault)

The system has detected the wrong number of indoor units or branch boxes connected.

Likely causes:

  • An indoor unit or branch box is not powered or not communicating
  • Wiring fault between units
  • Set-up error during installation

Safe checks before you call:

  • Turn the system off at the isolator or breaker for 5 to 10 minutes, then restart

What does Fujitsu General fault code 32 mean? (Current splits, ducted, multi-head and cassette systems (varies by series); on older three phase ducted systems (ARTC-LCTU, AUTA54LCLU) 32 instead means an indoor unit number set-up error, and on J Series multi systems E:32 means an outdoor unit fault; older AWT wall splits (AWT14/17LSAZ) use the same number for a different fault)

The main circuit board inside the indoor unit has failed or lost its stored settings.

Likely causes:

  • Indoor unit main PCB failure
  • EEPROM (stored model data) corruption, often after a power surge

Safe checks before you call:

  • Turn the system off at the isolator or breaker for 5 to 10 minutes, then restart

What does Fujitsu General fault code 39 mean? (Ducted systems (ARTG series) and larger wall splits (ASTG34LFCA and similar))

The circuit that drives the indoor fan motor has failed.

Likely causes:

  • Fan motor drive circuit failure on the indoor PCB
  • Fan motor fault overloading the circuit

Safe checks before you call:

  • Turn the system off at the isolator or breaker for 5 to 10 minutes, then restart

What does Fujitsu General fault code 41 mean? (Current splits, ducted, multi-head and cassette systems (varies by series))

The sensor that reads the room air temperature has failed.

Likely causes:

  • Failed room air thermistor
  • Loose sensor plug or damaged wiring
  • Indoor PCB fault

Safe checks before you call:

  • Turn the system off at the isolator or breaker for 5 to 10 minutes, then restart

What does Fujitsu General fault code 42 mean? (Current splits, ducted, multi-head and cassette systems (varies by series); older AWT wall splits (AWT14/17LSAZ) use the same number for a different fault)

The temperature sensor on the indoor coil (heat exchanger) has failed.

Likely causes:

  • Failed indoor coil thermistor
  • Loose sensor plug or damaged wiring
  • Indoor PCB fault

Safe checks before you call:

  • Turn the system off at the isolator or breaker for 5 to 10 minutes, then restart

What does Fujitsu General fault code 51 mean? (Current splits, ducted, multi-head and cassette systems (varies by series))

The indoor fan motor has failed or cannot spin properly.

Likely causes:

  • Seized or failed indoor fan motor
  • Fan blocked by an object or heavy dust build-up
  • Fan motor drive circuit fault

Safe checks before you call:

  • Turn the system off at the isolator or breaker for 5 to 10 minutes, then restart
  • Clean the return air filters if they are visibly clogged

What does Fujitsu General fault code 53 mean? (Current splits, ducted, multi-head and cassette systems (varies by series); older AWT wall splits (AWT14/17LSAZ) use the same number for a different fault)

The system has detected a condensate drainage problem, usually water not draining away.

Likely causes:

  • Blocked condensate drain line
  • Failed drain pump (ducted and cassette units)
  • Float switch stuck or faulty

Safe checks before you call:

  • Look at the drain outlet where it exits the wall and clear any visible leaves or dirt at the opening
  • Turn the system off at the isolator or breaker for 5 to 10 minutes, then restart

Fault confirmed? Here is what to do next

A fault code is the starting point, not the fix. Start here:

Call us on 08 8296 7888 or book online and we will call or text you back ASAP.

Sources for this page

Every Fujitsu General code above is checked against these Australian documents. Open them yourself to verify anything on this page:

Fujitsu General fault code FAQs

Where do I find the fault code on a Fujitsu General air conditioner?

Check the remote or wall controller display first. Some models flash the indoor unit’s lamps in a pattern instead; the table above lists documented lamp patterns alongside their codes. If nothing is showing, the code may only appear while the fault is active.

Can I clear a Fujitsu General fault code myself?

You can reset the system by turning it off at the isolator or breaker for five minutes. If the code stays gone, it was a one-off. If it returns, the fault is real and needs a licensed technician, and repeated resets can cause further damage on compressor or refrigerant faults.

Does a Fujitsu General fault code mean I need a new air conditioner?

Usually not. Most codes point to repairable faults like sensors, fan motors or drainage. Our fault find gives you an honest verdict either way, and the fee is credited if you repair with us.

Are these Fujitsu General fault codes correct for Australian models?

Yes. Every code on this page was checked against Australian documentation (assist.fujitsugeneral.com.au, valleyairconditioning.com.au, arma.org.au), not overseas lists, because the same code can mean different things in different markets. Meanings still vary between model series, so treat this page as reference and cross-check your unit’s manual.

Written by Oliver Hastings, T&K Airpower. Last updated 01/08/2026. Compiled from Australian sources including assist.fujitsugeneral.com.au, valleyairconditioning.com.au, arma.org.au, fujitsuairconditioningperth.com.au, so you can check every code against the official documentation. Fault code meanings vary between model series and controllers, so treat this page as reference only and never remove panels or work on the refrigeration or electrical parts of the system yourself.

T&K Airpower - Air Conditioner and Electrician Repair experts in Adelaide

Established, Local, and Accountable

We’ve been working in Adelaide homes for over 30 years.

Every job is done by our own technicians, employed, not subcontracted, so the person on your roof or at your switchboard is accountable for the work. We back it with a lifetime workmanship warranty, and we’ll be here to stand behind it long after the job is done.

ExcellentGoogle star 1Google star 2Google star 3Google star 4Google star 54.9671 reviews
4.9Google star 1Google star 2Google star 3Google star 4Google star 5
Excellent671 reviews
Posted on Google Google
Kaye Cleave profile picture
Kaye Cleave
81 days ago
Google star 1Google star 2Google star 3Google star 4Google star 5Trustindex verifies that the original source of the review is Google.
+0
Great service and professional staff. Thank you T& K Airpower. I'm very happy with my new air-conditioner and would highly recommended your company

Owner's reply
Thank you, Kaye! We're thrilled you're happy with your new air-conditioner and appreciate your kind recommendation. It was a pleasure assisting you! Thanks, Oliver and the T&K Airpower Team! 08 8296 7888

(Translated by Google, see original)
Posted on Google Google
Boti Nagy profile picture
Boti Nagy
140 days ago
Google star 1Google star 2Google star 3Google star 4Google star 5Trustindex verifies that the original source of the review is Google.
+0
Been having my home air conditioning serviced by T&K for years and always impressed with how this company operates. From booking an appointment with a repairman to job completion, this is a truly professional operation. But it hasn't lost the human touch. To my surprise and delight, my repairman Daniel rang to inform me he might be later than anticipated because the job he was completing was taking longer. He wasn't that late in the end and was friendly, genial and, most importantly, efficient and professional. Stayed true to the quoted price too, which didn't break the bank. Highly recommend T&K.

Owner's reply
Thank you so much for your review! Means the world to us hearing great feedback about our team! I will pass this on to Dan and the office Team 😊
Posted on Google Google
Jan Sutherland profile picture
Jan Sutherland
515 days ago
Google star 1Google star 2Google star 3Google star 4Google star 5Trustindex verifies that the original source of the review is Google.
+0
Quick, efficient and well priced. Technician was very polite, knowledgeable and completed the task with minimal fuss or disruption. Will definitely use this company in the future.

Owner's reply
Thank you, Jan! We're delighted to hear about your positive experience with our technician. We look forward to assisting you again whenever you need us. Thanks, Oliver and the T&K Airpower Team! 08 8296 7888

(Translated by Google, see original)
Posted on Google Google
Kosta Sotiropoulos profile picture
Kosta Sotiropoulos
561 days ago
Google star 1Google star 2Google star 3Google star 4Google star 5Trustindex verifies that the original source of the review is Google.
+2
As Director of CS Real Estate managing a Property Portfolio, one of our business objectives is that we only partner with quality suppliers / tradespeople. Working with high performing and reputable businesses is nonnegotiable. In late 2024 I contacted T&K Airpower for two separate maintenance jobs. From the moment I made contact with them, I found them to be extremely responsive, reliable and most importantly experts in what they do. There quotes and pricing is very competitive. And further to that, with each job I received a detailed invoice and photos of the works undertaken. I've attached some pictures of the new PC Board installed along with the new wall controller. I wouldn't hesitate recommending T&K Airpower, Cindy, Julie and the entire team do a great job. As a customer, I know my landlords are in great hands. Thank you to the team at T&K Airpower.

Owner's reply
Thank you, Kosta, for your thoughtful review and kind words about our team! We're thrilled to hear about your positive experience and look forward to continuing to support your property portfolio needs. Thanks, Oliver and the T&K Airpower Team! 08 8296 7888
Posted on Google Google
Aaron Albino profile picture
Aaron Albino
567 days ago
Google star 1Google star 2Google star 3Google star 4Google star 5Trustindex verifies that the original source of the review is Google.
+1
The guys were half an hour earlier than expected. Although it was nearly two weeks from when I put the warranty claim in with Hitachi.They were very thorough in their inspection and completely contradictory to the installers opinion who said it was a fault with the unit itself. The problem is still unresolved !

Owner's reply
We're sorry to hear this, Aaron. Please contact our customer service so we can assist you further and help resolve the issue promptly. Thanks, Oliver and the T&K Airpower Team! 08 8296 7888
Posted on Google Google
Davin & Jodie Pickard profile picture
Davin & Jodie Pickard
631 days ago
Google star 1Google star 2Google star 3Google star 4Google star 5Trustindex verifies that the original source of the review is Google.
+1
Excellent communication and on site service

Owner's reply
Thank you, Davin and Jodie, for your kind words! We're thrilled to hear you enjoyed our communication and on-site service. Your feedback motivates us to keep delivering quality service. Thanks, Oliver and the T&K Airpower Team! 08 8296 7888
Posted on Google Google
T & J Air Conditioning profile picture
T & J Air Conditioning
792 days ago
Google star 1Google star 2Google star 3Google star 4Google star 5Trustindex verifies that the original source of the review is Google.
+0
T & K were very professional. They handled our warranty claim with Mitsubishi Electric within a few days. The technician Nathan was great to deal with and communicated well.

Owner's reply
Thank you, Tom! We're glad to hear Nathan and the team at T & K provided you with excellent service. Your satisfaction with our warranty process means a lot to us.

(Translated by Google, see original)
Posted on Google Google
Charles Bartlett profile picture
Charles Bartlett
0 days ago
Google star 1Google star 2Google star 3Google star 4Google star 5Trustindex verifies that the original source of the review is Google.
Most excellent thorough friendly service. Makes a nice change from what you get elsewhere.
Posted on Google Google
Larry Rawlins profile picture
Larry Rawlins
1 days ago
Google star 1Google star 2Google star 3Google star 4Google star 5Trustindex verifies that the original source of the review is Google.
Great service, Ciaran was a very friendly and knowledgeable technician.
Posted on Google Google
Gilbertt Kat profile picture
Gilbertt Kat
4 days ago
Google star 1Google star 2Google star 3Google star 4Google star 5Trustindex verifies that the original source of the review is Google.
Cieran did our air conditioner service today. Very efficient, lovely guy, no fuss, explained thoroughly about the status of my unit. Thoroughly recommend!!

Owner's reply
Hi Gilbertt! Thanks heaps for taking the time to leave us a review, we really appreciate it. Great to hear Ciaran got your air conditioning servicing sorted in Tusmore. Give us a bell on 08 8296 7888 anytime you need a hand. Cheers, Oliver and the T&K Airpower team
Posted on Google Google
Lucia Puzella profile picture
Lucia Puzella
5 days ago
Google star 1Google star 2Google star 3Google star 4Google star 5Trustindex verifies that the original source of the review is Google.
We had our solar panel's serviced on the 9/9/26 by Tristan, I was extremely impressed and happy with his professionalism. We also have our air-conditioning service with them. I would highly recommend them, that's why they deserved a 5 star. Thankyou T&K Air-conditioning and Electrical.

Owner's reply
Hi Lucia! Thanks so much for the great review, it genuinely means a lot to the team. So glad we could help you out. Give us a call anytime on 08 8296 7888 if you ever need us. Cheers, Oliver and the T&K Airpower team
Posted on Google Google
Lyn and Wolfgang Zeidler profile picture
Lyn and Wolfgang Zeidler
7 days ago
Google star 1Google star 2Google star 3Google star 4Google star 5Trustindex verifies that the original source of the review is Google.
Efficient timely service

Owner's reply
Hi Lyn! Thanks so much for the great review, it genuinely means a lot to the team. So glad we could help you out. Give us a call anytime on 08 8296 7888 if you ever need us. Cheers, Oliver and the T&K Airpower team
Posted on Google Google
Mario Pepicelli profile picture
Mario Pepicelli
7 days ago
Google star 1Google star 2Google star 3Google star 4Google star 5Trustindex verifies that the original source of the review is Google.
Toby was excellent, a really skilled tradesman. Worked out the issue with the air conditioner explained the options available. Once I selected the option he carried out the repair works.

Owner's reply
Hi Mario! Thank you for the lovely review, it means a lot to us. We are always here on 08 8296 7888 if you need anything down the track. Cheers, Oliver and the T&K Airpower team
Posted on Google Google
Barbara Isaacson profile picture
Barbara Isaacson
7 days ago
Google star 1Google star 2Google star 3Google star 4Google star 5Trustindex verifies that the original source of the review is Google.
Extremely happy, very thorough and friendly been using T&K Airpower for some 20 years plus, and have never had to complain about their service. Had a Solar Health Check done, and an Electrical Switch Board Upgrade that was badly needed, service was second to none, highly recommend. Price all up was good, and peace of mind guaranteed. 😀😀

Owner's reply
Thanks so much for your kind words! Have a lovely weekend! 👍😁
Posted on Google Google
Jamin Stojsavljevic profile picture
Jamin Stojsavljevic
7 days ago
Google star 1Google star 2Google star 3Google star 4Google star 5Trustindex verifies that the original source of the review is Google.
Great experience. 1st place I’ll call now for repairs or a new system. Excellent technical knowledge, friendly, answered all of my questions. Fix and upgrade of my existing system was well done and installers were considerate, friendly and knowledgeable.

Owner's reply
Hi Jamin! Really appreciate the kind words, reviews like this mean a lot to us. Glad Jacob could look after your air conditioning repairs in WALKERVILLE. Do not hesitate to call us on 08 8296 7888 if you ever need us again. Cheers, Oliver and the T&K Airpower team
Posted on Google Google
Paul Maschgan profile picture
Paul Maschgan
10 days ago
Google star 1Google star 2Google star 3Google star 4Google star 5Trustindex verifies that the original source of the review is Google.
If you're looking for a company that provides excellent communication, tradespeople who arrive on time, outstanding workmanship (thanks Tristan & Jacob) and leave everything clean and tidy then T & K Airpower is the company you are looking for. From my first contact with the office staff through to the completion of the work, the entire process was professional and hassle free. Nothing was too much trouble, and the team was friendly, knowledgeable, and happy to answer any questions. After reading the reviews before choosing T & K Airpower, I had high expectations, and I am pleased to say they were spot on. I would not hesitate in recommending them to anyone looking for quality air conditioning service and installation.

Owner's reply
Thank you so much, Paul, for your thoughtful feedback! We're thrilled to hear that Tristan, Jacob, and the team delivered a seamless experience. Your recommendation means a lot to us. Thanks, Oliver and the T&K Airpower Team! 08 8296 7888

(Translated by Google, see original)
Posted on Google Google
Ben Nicholls profile picture
Ben Nicholls
11 days ago
Google star 1Google star 2Google star 3Google star 4Google star 5Trustindex verifies that the original source of the review is Google.
Always great service and advice from the T&K AirPower crew. Been using them forever, never any issues

Owner's reply
Hi Ben! Thanks heaps for taking the time to leave us a review, we really appreciate it. Great to hear Ciaran got your electrical servicing sorted in Hampstead Gardens. We are always here on 08 8296 7888 if you need anything down the track. Cheers, Oliver and the T&K Airpower team
Posted on Google Google
Bernard McCallum profile picture
Bernard McCallum
11 days ago
Google star 1Google star 2Google star 3Google star 4Google star 5Trustindex verifies that the original source of the review is Google.
Last week we had a replacement air conditioning system installed by T&K. Technicians Oliver/Kieran and Noah attended all day Wednesday 21/2/24. Oliver attended Friday 23/2/24. The work performed was outstanding. My wife and I rate very highly the service provided before the installation and during the installation. Should you consider utilising T&K you won’t regret it. What we rate very highly was the professionalism and meticulous care taken.

Owner's reply
Hi Bernard! Thanks so much for the great review, it genuinely means a lot to the team. So glad we could help you out. Give us a call anytime on 08 8296 7888 if you ever need us. Cheers, Oliver and the T&K Airpower team
Posted on Google Google
Malcolm Skilton profile picture
Malcolm Skilton
12 days ago
Google star 1Google star 2Google star 3Google star 4Google star 5Trustindex verifies that the original source of the review is Google.
I frequently base my assessment of any service provider on first contact. In the case of T&K Airpower Air Conditioning and Electrical, first contact was very positive. The quote I received was very reasonable (especially with the seniors discount), and I accepted that quote without needing to go to any other providers. The service tech (Nathan) arrived when scheduled and was very polite and helpful. He completed the required work efficiently, and within a very reasonable time frame. I would no hesitation in useing this company again.

Owner's reply
Hi Malcolm! Thanks heaps for taking the time to leave us a review, we really appreciate it. Great to hear Nathan got your air conditioning servicing sorted in Craigmore. Give us a call anytime on 08 8296 7888 if you ever need us. Cheers, Oliver and the T&K Airpower team
Posted on Google Google
Meg Michell profile picture
Meg Michell
14 days ago
Google star 1Google star 2Google star 3Google star 4Google star 5Trustindex verifies that the original source of the review is Google.
Fabulous service

Owner's reply
Hi Meg! Thanks so much for the great review, it genuinely means a lot to the team. So glad Ciaran could help you out with your air conditioning servicing in North Adelaide. We are always here on 08 8296 7888 if you need anything down the track. Cheers, Oliver and the T&K Airpower team
Posted on Google Google
Michael Cusack profile picture
Michael Cusack
14 days ago
Google star 1Google star 2Google star 3Google star 4Google star 5Trustindex verifies that the original source of the review is Google.
The guys were great. Very professional and personable. They worked hard and cleaned up before they left. Highly recommended and I would highly recommend them. So good these days to get prompt and professional help.

Owner's reply
Hi Michael! Really appreciate the kind words, reviews like this mean a lot to us. Glad Oliver could look after your air conditioning installation in Birdwood. We are always here on 08 8296 7888 if you need anything down the track. Cheers, Oliver and the T&K Airpower team
Posted on Google Google
Rosslyn Eftimiou profile picture
Rosslyn Eftimiou
15 days ago
Google star 1Google star 2Google star 3Google star 4Google star 5Trustindex verifies that the original source of the review is Google.
Ciaran was friendly and very professional. Excellent service

Owner's reply
Hi Rosslyn! Really appreciate the great review, thank you. So glad you were happy with the team, and don't hesitate to give us a call on 08 8296 7888 anytime. Cheers, Oliver and the T&K Airpower team
Posted on Google Google
Jodie Bradbrook profile picture
Jodie Bradbrook
21 days ago
Google star 1Google star 2Google star 3Google star 4Google star 5Trustindex verifies that the original source of the review is Google.
This business has exceptional customer service and lovely technicians. They do quality work and are great to deal with. Highly recommend.

Owner's reply
Hi Jodie! Thanks so much for the great review, it genuinely means a lot to the team. So glad Tristan could help you out with your air conditioning repairs over in Richmond. Give us a call anytime on 08 8296 7888 if you ever need us. Cheers, Oliver and the T&K Airpower team
Posted on Google Google
ZoZo's YouTube Channel profile picture
ZoZo's YouTube Channel
21 days ago
Google star 1Google star 2Google star 3Google star 4Google star 5Trustindex verifies that the original source of the review is Google.
Prompt and professional service

Owner's reply
Hi ZoZo's! Really appreciate the great review, thank you. So glad you were happy with the team, and don't hesitate to give us a call on 08 8296 7888 anytime. Cheers, Oliver and the T&K Airpower team
Posted on Google Google
Peter Dalton profile picture
Peter Dalton
21 days ago
Google star 1Google star 2Google star 3Google star 4Google star 5Trustindex verifies that the original source of the review is Google.
We were being gassed by an old Daiken air conditioner losing its refrigerant and causing headaches in our Study. We called T&K AirPower through our RAA membership, their technician / salesman Toby arrived promptly and was able to spot the problem then present options which became a reasonably priced new Mitsubishi unit which we coupled with another unit for our adjacent Guest Bedroom working off the same fan coil unit. He spent time on a solution for an on roof mounted unit for our Family Room. The installation team Oliver, Luke and Giaran did a great install including a new electrical circuit. Definitely a 5 Star review but for a couple of old dodgy baby boomers, I was impressed with the ease of communication and professionalism.

Owner's reply
Hi Peter! Thanks heaps for the kind review, we really appreciate you taking the time. Glad we could get you sorted, and give us a bell on 08 8296 7888 if you ever need a hand. Cheers, Oliver and the T&K Airpower team
Posted on Google Google
Sam Catley profile picture
Sam Catley
24 days ago
Google star 1Google star 2Google star 3Google star 4Google star 5Trustindex verifies that the original source of the review is Google.
A great big thankyou to Toby, Oliver, Nick, Noah & the T&K Air Team for your brilliant service. You were professional, knowledgeable & surpassed our expectations. We are thrilled with our new ducted aircon.

Owner's reply
Hi Sam! Thank you for the lovely review, the team was stoked to see it. So good to hear Noah took care of your air conditioning installation for you in Prospect. Do not hesitate to call us on 08 8296 7888 if you ever need us again. Cheers, Oliver and the T&K Airpower team
Posted on Google Google
Winston Head profile picture
Winston Head
25 days ago
Google star 1Google star 2Google star 3Google star 4Google star 5Trustindex verifies that the original source of the review is Google.
Toby is a very knowledgeable, he explained many things about our AC that we had no idea about. He suggested several things that would make our unit run better and more efficiently, saving $$$ and work. We have no hesitation in recommending Toby for any AC service.

Owner's reply
Hi Winston! Thanks heaps for taking the time to leave us a review, we really appreciate it. Great to hear Tobias got your air conditioning servicing sorted in Highbury. Do not hesitate to call us on 08 8296 7888 if you ever need us again. Cheers, Oliver and the T&K Airpower team
Posted on Google Google
Lyn Jefferies profile picture
Lyn Jefferies
28 days ago
Google star 1Google star 2Google star 3Google star 4Google star 5Trustindex verifies that the original source of the review is Google.
Great service & prompt attention. Good price for a country job too.

Owner's reply
Thank you, Lyn! We're thrilled you were pleased with our service and pricing. Your feedback means a lot to us!
Posted on Google Google
Bob Aston profile picture
Bob Aston
28 days ago
Google star 1Google star 2Google star 3Google star 4Google star 5Trustindex verifies that the original source of the review is Google.
Great service. Kieran was right on time, went about the job in an efficient and organised way and completed it within the given timeframe. Cost as expected. We would recommend the company any time.

Owner's reply
Thank you, Bob! We're thrilled to hear about your positive experience with Kieran. Your recommendation means a lot to us and we look forward to assisting you again in the future. Thanks, Oliver and the T&K Airpower Team! 08 8296 7888
Posted on Google Google
Sally Huefner profile picture
Sally Huefner
30 days ago
Google star 1Google star 2Google star 3Google star 4Google star 5Trustindex verifies that the original source of the review is Google.
Last thing you need mid winter is the heating to stop working so a call to T&K and Toby was out to diagnose and fix the system. Great service, quickly found the problem, had the part on the van and soon it was warm again inside. Highly recommended Toby and the team at T&K AirPower.

Owner's reply
Hi Sally! Thanks so much for the great review, it genuinely means a lot to the team. So glad Tobias could help you out with your air conditioning repairs over in Hazelwood Park. Give us a call anytime on 08 8296 7888 if you ever need us. Cheers, Oliver and the T&K Airpower team
Posted on Google Google
Daniel Dieckmann profile picture
Daniel Dieckmann
30 days ago
Google star 1Google star 2Google star 3Google star 4Google star 5Trustindex verifies that the original source of the review is Google.
Happy with Jacob on a/c service and replacement 2 fan motors. All working well.

Owner's reply
Hi Daniel! Thanks so much for the great review, it genuinely means a lot to the team. So glad Jacob could help you out with your air conditioning repairs in Glengowrie. Give us a bell on 08 8296 7888 anytime you need a hand. Cheers, Oliver and the T&K Airpower team
Posted on Google Google
Mike Munday profile picture
Mike Munday
31 days ago
Google star 1Google star 2Google star 3Google star 4Google star 5Trustindex verifies that the original source of the review is Google.
We contacted T&K Airpower to arrange some repairs on our Temperzone air conditioner. I called them on a Thursday and they had a technician (Toby) available on the following Monday morning 3 August. Our controller was not working properly and stopped working altogether the day before Toby came. When he arrived he checked what we wanted done and which we discussed with him. He said he wanted to have a look at the unit outside to see if he could at least get the air conditioner working. As he was doing this a solenoid fused with a large bang so he couldn’t do anything else until that part was replaced. He contacted the office to arrange a quote so they could commence sourcing the parts. The controller took longer than expected to source and the job was booked in for Friday 14 August but due to another job being postponed we had our job brought forward to Wednesday 12 August which was most appreciated due to having a very cold house during this period. The technician that completed our work was Artie and he was absolutely fantastic. When he arrived we went through everything that had to be done which we were advised would take up to about 5 hours. The new controller had to be completely re wired, the new solenoid fitted and the whole system serviced. We also replaced 3 hard wired fire alarms replaced. Artie was very tidy and respectful and polite in every way. We would request his services if that was possible should we have any further issues that need attention. Also the young ladies in the office being Alicia and Ebony were also very helpful and courteous every time I dealt with them on the phone. The total cost was just over $2300 which we thought was reasonable for the efficiency and the job being completed by a quality technician in Artie.

Owner's reply
Hi Mike! Thank you for the lovely review, it means a lot to us. We are always here on 08 8296 7888 if you need anything down the track. Cheers, Oliver and the T&K Airpower team
Posted on Google Google
Travers Gebler profile picture
Travers Gebler
31 days ago
Google star 1Google star 2Google star 3Google star 4Google star 5Trustindex verifies that the original source of the review is Google.
On-time, very easy to deal with. Enthusiastic & polite crew. Recommend for sure.

Owner's reply
Hi Travers! Thank you for the lovely review, the team was stoked to see it. So good to hear Noah took care of your air conditioning installation for you in Kidman Park. Do not hesitate to call us on 08 8296 7888 if you ever need us again. Cheers, Oliver and the T&K Airpower team
Posted on Google Google
Chris Boyd profile picture
Chris Boyd
31 days ago
Google star 1Google star 2Google star 3Google star 4Google star 5Trustindex verifies that the original source of the review is Google.
Excellent communication, professional conduct, and reasonable price

Owner's reply
Hi Chris! Really appreciate the kind words, reviews like this mean a lot to us. Glad Tristan could look after your air conditioning servicing in Virginia. We are always here on 08 8296 7888 if you need anything down the track. Cheers, Oliver and the T&K Airpower team
Posted on Google Google
Petre Thorn profile picture
Petre Thorn
32 days ago
Google star 1Google star 2Google star 3Google star 4Google star 5Trustindex verifies that the original source of the review is Google.
Toby was on time, professional and knowledgeable.

Owner's reply
Hi Petre! Really appreciate the great review, thank you. So glad you were happy with the team, and don't hesitate to give us a call on 08 8296 7888 anytime. Cheers, Oliver and the T&K Airpower team
Posted on Google Google
Phil Bancroft profile picture
Phil Bancroft
35 days ago
Google star 1Google star 2Google star 3Google star 4Google star 5Trustindex verifies that the original source of the review is Google.
Arrived on time. Very friendly. Explained everything. Always very happy.

Owner's reply
Hi Phil! Thanks heaps for the kind review, we really appreciate you taking the time. Glad we could get you sorted, and give us a bell on 08 8296 7888 if you ever need a hand. Cheers, Oliver and the T&K Airpower team
Posted on Google Google
Kate G profile picture
Kate G
35 days ago
Google star 1Google star 2Google star 3Google star 4Google star 5Trustindex verifies that the original source of the review is Google.
Nathan was efficient, friendly and provided useful information. Thanks

Owner's reply
Hi Kate! Thanks so much for the great review, it genuinely means a lot to the team. So glad we could help you out. Give us a call anytime on 08 8296 7888 if you ever need us. Cheers, Oliver and the T&K Airpower team
Posted on Google Google
babis babas profile picture
babis babas
35 days ago
Google star 1Google star 2Google star 3Google star 4Google star 5Trustindex verifies that the original source of the review is Google.
We could not be happier. Great service and our system has never worked so well before! Thanks guys.

Owner's reply
Hi babis! Really appreciate the great review, thank you. So glad you were happy with the team, and don't hesitate to give us a call on 08 8296 7888 anytime. Cheers, Oliver and the T&K Airpower team
Posted on Google Google
yueqiang zhang profile picture
yueqiang zhang
36 days ago
Google star 1Google star 2Google star 3Google star 4Google star 5Trustindex verifies that the original source of the review is Google.
Good service. Thanks Toby and T&K. Will be looking for some discounts for next service

Owner's reply
Hi yueqiang! Thank you for the lovely review, it means a lot to us. We are always here on 08 8296 7888 if you need anything down the track. Cheers, Oliver and the T&K Airpower team
Posted on Google Google
Angie Evans profile picture
Angie Evans
40 days ago
Google star 1Google star 2Google star 3Google star 4Google star 5Trustindex verifies that the original source of the review is Google.
Nathan arrived promptly, was friendly, completed the task required and provided information for future work. Pleased we chose T&K

Owner's reply
Hi Angie! Thank you for the lovely review, it means a lot to us. We are always here on 08 8296 7888 if you need anything down the track. Cheers, Oliver and the T&K Airpower team
Posted on Google Google
Mark Seatree profile picture
Mark Seatree
40 days ago
Google star 1Google star 2Google star 3Google star 4Google star 5Trustindex verifies that the original source of the review is Google.
Marty is a legend!

Owner's reply
Hi Mark! Thanks heaps for taking the time to leave us a review, we really appreciate it. Great to hear Martin got your air conditioning repairs sorted in Rostrevor. Give us a bell on 08 8296 7888 anytime you need a hand. Cheers, Oliver and the T&K Airpower team
Posted on Google Google
Maris Javier profile picture
Maris Javier
41 days ago
Google star 1Google star 2Google star 3Google star 4Google star 5Trustindex verifies that the original source of the review is Google.
Toby is an excellent worker. He was respectful and was very efficient. I would say one of the best I've dealt with. Thank you Toby for your competence and professionalism!

Owner's reply
Hi Maris! Thanks heaps for the kind review, we really appreciate you taking the time. Glad we could get you sorted, and give us a bell on 08 8296 7888 if you ever need a hand. Cheers, Oliver and the T&K Airpower team
Posted on Google Google
Volker Trede profile picture
Volker Trede
42 days ago
Google star 1Google star 2Google star 3Google star 4Google star 5Trustindex verifies that the original source of the review is Google.
Quick turn around, excellent communication. Will use again.

Owner's reply
Hi Volker! Really appreciate the great review, thank you. So glad you were happy with the team, and don't hesitate to give us a call on 08 8296 7888 anytime. Cheers, Oliver and the T&K Airpower team
Posted on Google Google
Ken AY profile picture
Ken AY
42 days ago
Google star 1Google star 2Google star 3Google star 4Google star 5Trustindex verifies that the original source of the review is Google.
Used them to investigate an issue with a ducted AC system, attended by professional and experienced technicians who were able to quickly identify and fix the problem.

Owner's reply
Hi Ken! Thank you for the lovely review, it means a lot to us. We are always here on 08 8296 7888 if you need anything down the track. Cheers, Oliver and the T&K Airpower team
Posted on Google Google
jo Stone profile picture
jo Stone
45 days ago
Google star 1Google star 2Google star 3Google star 4Google star 5Trustindex verifies that the original source of the review is Google.
Amazing service. Excellent and trustworthy staff. Highly recommend. Service was easy and delivered with quality. Thank you

Owner's reply
Hi jo! Thank you for the lovely review, the team was stoked to see it. So good to hear Tobias took care of your air conditioning installation for you in Panorama. Give us a call anytime on 08 8296 7888 if you ever need us. Cheers, Oliver and the T&K Airpower team
Posted on Google Google
Bianca Davidson profile picture
Bianca Davidson
45 days ago
Google star 1Google star 2Google star 3Google star 4Google star 5Trustindex verifies that the original source of the review is Google.
Lovely experience with technician Tristan. He walked me through every step, explained what would benefit my split system and gave me a run down of all my options.

Owner's reply
Hi Bianca! Thank you for the lovely review, the team was stoked to see it. So good to hear Tristan took care of your air conditioning servicing for you in Ingle Farm. Give us a call anytime on 08 8296 7888 if you ever need us. Cheers, Oliver and the T&K Airpower team
Posted on Google Google
Adrian Hocking profile picture
Adrian Hocking
46 days ago
Google star 1Google star 2Google star 3Google star 4Google star 5Trustindex verifies that the original source of the review is Google.
Absolutely Excellent Service and VERY HAPPY With the price. Service man was very nice and very polite. Thank you so much...

Owner's reply
Hi Adrian! Really appreciate the kind words, reviews like this mean a lot to us. Glad Tristan could look after your air conditioning repairs in Craigmore. We are always here on 08 8296 7888 if you need anything down the track. Cheers, Oliver and the T&K Airpower team
Posted on Google Google
Michael Bowes profile picture
Michael Bowes
47 days ago
Google star 1Google star 2Google star 3Google star 4Google star 5Trustindex verifies that the original source of the review is Google.
Excellent and honest service from Marty

Owner's reply
Hi Michael! Really appreciate the kind words, reviews like this mean a lot to us. Glad Martin could look after your air conditioning repairs in Belair. Do not hesitate to call us on 08 8296 7888 if you ever need us again. Cheers, Oliver and the T&K Airpower team
Posted on Google Google
Kerry Leaver profile picture
Kerry Leaver
48 days ago
Google star 1Google star 2Google star 3Google star 4Google star 5Trustindex verifies that the original source of the review is Google.
Received fantastic service, advice and support from Toby today. He communicated really well, spent time explaining what the issues were and what my options were. Then the replacement parts I needed were couriered over while Toby waited and my heating was working before he left. So efficient! He also spotted that my smoke alarm was expired which I had not asked him to check.

Owner's reply
Hi Kerry! Really appreciate the kind words, reviews like this mean a lot to us. Glad Tobias could look after your air conditioning repairs in Somerton Park. We are always here on 08 8296 7888 if you need anything down the track. Cheers, Oliver and the T&K Airpower team
Posted on Google Google
Tom profile picture
Tom
49 days ago
Google star 1Google star 2Google star 3Google star 4Google star 5Trustindex verifies that the original source of the review is Google.
We initially had a temporary repair of our old air conditioner. That worked well but a new one was clearly the way to go. The service was uniformly prompt and outstanding. Tobi deserves particular credit for his professional, thorough and non-pushy contribution. Highly recommended. Tom Stubbs

Owner's reply
Hi Tom! Thanks heaps for the kind review, we really appreciate you taking the time. Glad we could get you sorted, and give us a bell on 08 8296 7888 if you ever need a hand. Cheers, Oliver and the T&K Airpower team
Verified by Trustindex
Trustindex verified badge is the Universal Symbol of Trust. Only the greatest companies can get the verified badge who has a review score above 4.5, based on customer reviews over the past 12 months. Read more
null

With Over 30 Years of Experience, You Can Trust Our Certified Technicians To Do The Job Right The FIRST TIME for your air conditioner and electrician needs.

null

Honest Advice on Your Home's Comfort, Energy and Safety

Every price and answer on this page comes from the same pricing and diagnostics our own technicians use, so what you see is a genuine indication, not a teaser.

Where an upgrade is genuinely needed, we’ll explain why in plain terms and set out your best option. No pressure, no unnecessary work.

We only recommend it when it improves safety, reliability or long-term performance.

We’ll call or text you back ASAP!

Bright green logo with sunburst design

Service Area

null

Servicing Adelaide Homes and Surrounding Suburbs

We provide residential electrical energy solutions and upgrades across metropolitan Adelaide, including inner eastern, western and southern suburbs